Plan Review Notes
Plan Review Notes For Permit 16010349
Permit Number 16010349
Review Stop M
Sequence Number 1
Notes
Date Text
2016-01-14 11:42:261ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010349
 01/14/16
  
 1) THE EQUIPMENT SCHEDULES ON M-3 ARE NOT LEGIBLE AND
 WILL NOT BE ABLE TO BE SCANNED AND COPIED FOR PUBLIC
 RECORD FILING- REFER TO SECTION 107.2.1 WPB AMENDMENTS
 TO THE FBC-10 BUILDING.
 2) THE PLANS SHALL BE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD BARRY P. PITTS P.E. IN ACCORDANCE WITH
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. THE
 SEAL MUST BE A RAISED SEAL OR INK SEAL: ELECTRONIC
 SEALS ON PAPER PLANS ARE NOT ACCEPTED BY THE WPB
 CONSTRUCTION SERVICES DEPT.
 3) SHEET S-1: PROVIDE THE WIND LOAD DESIGN CRITERIA
 INCLUDING: WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 A) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 B) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  