| Plan Review Notes For Permit 16010345 |
| Permit Number |
16010345 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-16 07:26:09 | 1) THE ENGINEERING FOR THE GAS HEATER ANCHORING IS | | | BASED ON THE 2010 FBC. THE CODE IN EFFECT IS THE 2014 | | | FBC. | | | 2) THE ENGINEERING DOCUMENT FOR THE POOL HEATER | | | ANCHORING IS A COPY OF ANORIGINAL SIGNED AND SEALED | | | DOCUMENT. F.A.C. RULE 61G15-23.001 REQUIRES DOCUMENTS | | | PREPARED BY THE DESIGNER TO BEAR THE SEAL AND SIGNATURE | | | OF THE ENGINEER OF RECORD.SUBMIT THE REQUIRED SIGNED | | | AND SEALED DOCUMENT FOR REVIEW. THE ENGINEER FOR THE | | | WIND DESIGN IS DIFFERENT THAN THE ENGINEER FOR THE POOL | | | DESIGN. CLARIFY.ALSO, CHECK THE EXPOSURE. IT IS CALLED | | | OUT AS EXPOSSURE D. | | | 3) THE LOCATION OF THE POOL EQUIPMENT ON THE POOL PLAN | | | DOES NOT CORRELATE WITH THE POOL PLAN. CLARIFY. | | | 4) R403.9.2 TIME SWITCHES. | | | TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN | | | AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS | | | ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON | | | ALL HEATERS AND PUMPS. HEATERS, PUMPS AND MOTORS THAT | | | HAVE BUILT IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH | | | THIS REQUIREMENT. | | | 5) R403.9.3 COVERS. | | | HEATED SWIMMING POOLS AND INGROUND PERMANENTLY | | | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT | | | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR | | | OTHER MEANS PROVEN TO REDUCE HEAT LOSS. | | | |
|