| Plan Review Notes For Permit 16010338 |
| Permit Number |
16010338 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-28 05:01:01 | 1) THE LAVATORIES IN THE MASTER BATH ARE NOT VENTED. | | | 2014 FBCR SEC.P3101.2. | | | 2) A VENT IS REQD. BETWEEN THE TUB & SHOWER IN THE | | | MASTER BATH. 2014 FBCR SEC.P3101.2. | | | 3) BATH #2 - A VENT IS REQUIRED BETWEEN THE WATER | | | CLOSET AND THE SHOWER. 2014 FBCR SEC.P3101.2. | | | 4) BATH #3 - A VENT IS REQUIRED BETWEEN THE WATER | | | CLOSET AND THE SHOWER. 2014 FBCR SEC.P3101.2. | | | 5) A VENT IS REQUIRED ON THE WASHING MACHINE. 2014 FBCR | | | SEC.P3101.2. | | | 6) THE WASHING MACHINE AND LAVATORY CANNOT DISCHARGE | | | INTO THE WASTE STACK AT THE SAME LEVEL PER 2014 FBCR | | | SEC.P3005.1.1. | | | 7) CLEANOUTS ARE REQUIRED IN THE BASE OF SOIL % WASTE | | | STACKS PER 2014 FBCR SEC. P3005.2.6. | | | 8) SEPARATE PLANS AND PERMIT ARE REQUIRED FOR THE GAS | | | PIPING INSTALLATION. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|