| 2016-02-11 11:09:24 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA. THE PROPOSED WORK IS AN ADDITION AND SUBSTANTIAL |
| | IMPROVEMENT TO THE EXISTING STRUCTURE. THE CITY OF WEST |
| | PALM BEACH'S FLOOD ORDINANCE, FEMA AND THE 2014 FLORIDA |
| | BUILDING CODE RESIDENTIAL REQUIRE THE STRUCTURE TO |
| | COMPLY WITH THE FLOOD ORDINANCE. THE MINIMUM FINISH |
| | FLOOR ELEVATION IS REQUIRED TO BE 7.5' NGVD 1929. |
| | SPECIFY THE FINISH FLOOR ELEVATIONS ON THE PLANS BASED |
| | ON NGVD 1929 AND SUBMIT A PRECONSTRUCTION ELEVATION |
| | CERTIFICATE. |
| | |
| | 2) A SEPARATE PERMIT, APPLICATION AND PLANS ARE |
| | REQUIRED FOR THE ELECTRIC GENERATOR. FBC 105.1 |
| | |
| | 3) THE COMPONENT AND CLADDING PRESSURES ON SHEETS A-3 |
| | ARE INCORRECT FOR THE SECTIONAL GARAGE DOOR AND FRENCH |
| | DOORS ON THE PROPOSED WEST ELEVATION. BASED ON FBCR |
| | TABLES R301.2(2), R301.2(3) AND R301.2(4) THE SPECIFIED |
| | PRESSURES ARE LOWER THAN REQUIRED. |
| | |
| | 4) THE DOOR SCHEDULE ON A-7 SPECIFIES A GLASS PANEL ON |
| | TOP OF THE ENTRY DOOR, BUT NOT SIDELITES ON EACH SIDE |
| | AS SHOWN ON THE FLOOR PLAN AND ELEVATIONS ON SHEETS A-1 |
| | AND A-3. PLEASE CLARIFY. SPECIFY THE SIZES OF THE |
| | SIDELITES AND THE TRANSOM ON THE PLANS. FBC 107.2.1 |
| | |
| | 5) ON SHEET S-2 ROOF FRAMING NOTE #6 REFERENCES THE |
| | 2010 FBC AND THE 2014 FBC SHOULD BE REFERENCED. |
| | |
| | 6) ON SHEET E-1 THE GENERAL ELECTRICAL NOTES REFERENCES |
| | THE 2008 NEC AND THE 2011 NEC SHOULD BE REFERENCED. |
| | |
| | 7) THE WINDOW SCHEDULE ON SHEET A-7 SPECIFIES DOUBLE |
| | HUNG WINDOWS AND THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE CLARIFY. |
| | FBC 107.2.1 |
| | |
| | 8) THE PLANS SPECIFY DOUBLE OUTSWING WOOD FRENCH DOORS |
| | WITH AND WITHOUT SIDELITES. THE PRODUCT APPROVALS THAT |
| | WERE SUBMITTED ARE FOR SINGLE OUTSWING ALUMINUM FRENCH |
| | DOORS W/WO SIDELITES. SUBMIT PRODUCT APPROVALS FOR THE |
| | DOORS THAT WILL BE USED. FBC 107.2.1 & DCA RULE 9N-72 |
| | |
| | 9) SUBMIT TWO SETS OF THE CURRENT ICC-ES EVALUATION |
| | REPORTS FOR THE SPRAY FOAM INSULATION THAT WILL BE |
| | INSTALLED. FBC-R316 |
| | |
| | 10) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS, |
| | LISTING AND INSTALLATION INSTRUCTIONS FOR THE FACTORY |
| | BUILT GAS FIREPLACE AND CHIMNEY. FBC-R1005 |
| | |
| | 11) PROVIDE STRUCTURAL DETAILS FOR THE FIREPLACE AND |
| | CHIMNEY. FBC 107.2.1 |
| | |
| | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |