Plan Review Notes
Plan Review Notes For Permit 16010296
Permit Number 16010296
Review Stop G
Sequence Number 1
Notes
Date Text
2016-01-14 05:48:411) THE DESCRIPTION OF WORK ON THE APPLICATION NOTES
 "REPAIR EXISTING GAS LINE" BUT THERE IS NOTHING ON THE
 PLANS THAT REFLECTS THE SCOPE OF WORK TO BE DONE. IF
 THIS A "REPAIR", THEN CLEARLY DESCRIBE ON THE PLANS
 WHAT "REPAIRS" ARE BEING DONE. IF THE ENTIRE GAS LINE
 IS BEING REPLACED, NOTE SO ON THE APPLICATION AND ON
 THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZES OF ALL THE SECTIONS OF PIPE.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE PSI OF THE SYSTEM ON THE PLANS.
 4) INDICATE THE TYPE OF PIPING TO BE INSTALLED [CSST,
 PE (UNDERGROUND), GALVANIZED].
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  