| Plan Review Notes For Permit 16010296 |
| Permit Number |
16010296 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-14 05:48:41 | 1) THE DESCRIPTION OF WORK ON THE APPLICATION NOTES | | | "REPAIR EXISTING GAS LINE" BUT THERE IS NOTHING ON THE | | | PLANS THAT REFLECTS THE SCOPE OF WORK TO BE DONE. IF | | | THIS A "REPAIR", THEN CLEARLY DESCRIBE ON THE PLANS | | | WHAT "REPAIRS" ARE BEING DONE. IF THE ENTIRE GAS LINE | | | IS BEING REPLACED, NOTE SO ON THE APPLICATION AND ON | | | THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHOW THE PIPE SIZES OF ALL THE SECTIONS OF PIPE.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 3) SHOW THE PSI OF THE SYSTEM ON THE PLANS. | | | 4) INDICATE THE TYPE OF PIPING TO BE INSTALLED [CSST, | | | PE (UNDERGROUND), GALVANIZED]. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|