2016-04-06 17:03:51PLUMBING COMMENTS: 2ND REVIEW 2ND REQUEST
  
 1. BREAK ROOM SINK SHALL COMPLY WITH FBC ACC. SEC.
 606.3 FRONT EDGE OF SINK SHALL BE 34" MAX IN HEIGHT.
 606.2. SHOW CLEAR FLOOR SPACE PARALLEL APPROACH OR
 FRONT APPROACH.
  
 2. SHOW SHOWER CONTROL VALVE TO COMPLY WITH FBC ACC
 SEC. 680.5.2L
  
 3. A SEPARATE PERMIT IS REQUIRED FOR 1" RPZ BACKFLOW ON
 WATER MAIN.
  
  