| Plan Review Notes For Permit 16010290 |
| Permit Number |
16010290 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-06 17:03:51 | PLUMBING COMMENTS: 2ND REVIEW 2ND REQUEST | | | | | | 1. BREAK ROOM SINK SHALL COMPLY WITH FBC ACC. SEC. | | | 606.3 FRONT EDGE OF SINK SHALL BE 34" MAX IN HEIGHT. | | | 606.2. SHOW CLEAR FLOOR SPACE PARALLEL APPROACH OR | | | FRONT APPROACH. | | | | | | 2. SHOW SHOWER CONTROL VALVE TO COMPLY WITH FBC ACC | | | SEC. 680.5.2L | | | | | | 3. A SEPARATE PERMIT IS REQUIRED FOR 1" RPZ BACKFLOW ON | | | WATER MAIN. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|