Plan Review Notes
Plan Review Notes For Permit 16010290
Permit Number 16010290
Review Stop M
Sequence Number 2
Notes
Date Text
2016-03-29 07:39:012ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010290
 3/29/16
  
 ALTHOUGH THE NARRATIVE RESPONSE FROM FAE CONSULTING IS
 INDICATING ALL 1ST REVIEW COMMENTS HAVE BEEN ADDRESSED,
 IT APPEARS THAT MANY OF THE ISSUES STILL EXIST.
 RE-PRINTED BELOW ARE 1ST REVIEW COMMENTS THAT STILL
 EXIST.
  
 1) THE AC SYSTEM SIZING CALCULATIONS ARE INDICATING
 INCORRECT CLIMATE DATA FROM MIAMI: PLEASE PROVIDE WEST
 PALM BEACH AS THE LOCATION AND SOURCE OF CLIMATE DATA.
 2) THE ENERGY FORM 506-2014 IS INDICATING CAPACITIES
 FOR AHU-1 & 2 THAT DIFFER FROM THE CAPACITIES ON THE AC
 SCHEDULE- SHEET M0-1.
 3) SHEET M1.2: THE O/A DUCTS FOR AHU-1 APPEARS TO BE
 PENETRATING THE FIRE-RATED EXIT STAIRWAY CEILING,
 FLOOR, AND WALL WHICH IS PROHIBITIED BY SECTION 1022.5
 FBC-14 BUILDING. IF THE THE DUCT IS TO REMAIN IN THE
 STAIRWAY IT MUST BE IN A FIRE-RATED ENCLOSURE, AND A
 DAMPER IS REQUIRED AT THE FIRE-RATED FLOOR CEILING
 ASSEMBLY.
 5) M1.1: THE RETURN AIR TRANSFER DUCT SHALL BE SIZED
 1.5 TIMES THE CROSS-SECTIONAL AREAS OF THE SUPPLY DUCTS
 ENTERING THE ROOM OR 252 SQ. INCHES. SEE SECTION 601.5
 FBC-14 MECHANICAL AND INCREASE THE SIZE OF THE DUCT
 ACCORDINGLY.
 7) M0.2: PLEASE PROVIDE THE WIND LOAD DESIGN CRITERIA
 (BASIC WIND SPEED AND CONVERSION, EXPOSURE CATEGORY,
 IMPORTANCE FACTOR, HEIGHT AND EXPOSURE COEFFICIENT
 ETC.) USED TO ESTABLISH THE CU TO ROOF STAND ATTACHMENT
 DETAILS- SEE SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  