| 2016-04-05 14:52:32 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010290 |
| | ADD: 805 N. RAILROAD AVE. |
| | CONT: PALM BEACH CAST STONE |
| | TEL: 561-835-4085 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. APRIL 04/2016 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED |
| | |
| | 3)2ND REQUEST. THE STRUCTURAL SHEET 5.1 SHOWS NEW STEEL |
| | COLUMNS BEING WELDED TO AN EXISTING W20X BEAM AS WELL |
| | AS NEW STEEL COLUMNS BEING WELDED ON THE 2ND FLOOR TO |
| | THE EXISTING W20X BEAM. NORMALLY THIS WOULD REQUIRE A |
| | RESIDENT INSPECTOR FOR BOLTED AND WELDED CONNECTIONS. |
| | 110.3.9 OTHER INSPECTIONS SERVICES7. FOR BUILDINGS AND |
| | STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION, BOLTED AND WELDED CONNECTIONS. PLEASE |
| | CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD TO SEE |
| | IF HE WILL REQUIRE THE RESIDENT INSPECTOR OR IF A |
| | WELDING CERTIFICATE FROM THE ONSITE WELDER WILL SUFFICE |
| | AND THE USE OF CITY BUILDING INSPECTORS. |
| | KEN CONRAD TEL: 561-805-6666. |
| | |
| | 4)SEMI-COMPLIED. PLEASE NOTE SHEETS A2.1 AND A2.2 THE |
| | 1ST FLOOR PLAN AND 2ND FLOOR PLAN DO HAVE WALL |
| | IDENTIFICATION TAGS THIS REVIEW. ON BOTH FLOORS THERE |
| | IS AN OCCUPANCY SEPARATION WALL THAT SEPARATES THE |
| | BUSINESS OCCUPANCY FROM THE S1 OCCUPANCY. SHEET A201 & |
| | A202 SHOW MOST OF THE WALL WITH A 1 HOUR OCCUPANCY |
| | SEPARATION, ONLY THE NEW BATH WALL ON THE 2ND FLOOR |
| | SHOWS A 2 HOUR FIRE RATING. PLEASE ALSO NOTE THE |
| | OPENING PROTECTIVES IN THIS 2 HOUR WALL WILL BE |
| | REQUIRED TO BE 1 ? HOUR OPENING PROTECTIVES SEE TABLE |
| | 716.5 OF THE 2014 FBC-B. |
| | |
| | THE OTHER ISSUE WITH THE RATED WALLS, THEY ARE ALL |
| | SHOWN AS NON-BEARING WALLS, THE STRUCTURAL SHEETS SHOW |
| | COLUMNS THAT DO NOT SHOW ON THE ARCHITECTURAL SHEETS. |
| | PLEASE ALSO NOTE THE STAIR MID-LANDING WILL NEED TO BE |
| | STRUCTURAL WITH BRACING TO TAKE THE LOADS ON THE |
| | STRINGERS SINCE THE WALLS THAT CREATE THE FIRE RATED |
| | WALLS ARE ALSO NON-LOADBEARING. THE PLANS ARE NOT CLEAR |
| | IN THIS AREA. ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. 107.2.1.3. |
| | |
| | 5A) SEMI ?COMPLIED, THERE IS A 2 HOUR OCCUPANCY WALL |
| | AND OPENING PROTECTIVES. SEE COMMENT # 6. SHEET A2.1 |
| | SHOWS (2) ROOMS LOCATED BENEATH THE STAIRS, THE |
| | RESTROOM 102 AND THE MECHANICAL ROOM 103. NOT HAVING A |
| | WALL LEGEND THAT IDENTIFIES THE TYPE OF WALLS PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2014 FBC-B; |
| | 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. |
| | THE WALLS CEILINGS AND SOFFITS WITHIN ENCLOSED USABLE |
| | SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR |
| | ENCLOSURE. |
| | |
| | 5B) SEMI ?COMPLIED, THERE IS A 2 HOUR OCCUPANCY WALL |
| | AND OPENING PROTECTIVES. SEE COMMENT # 6. THE BATHROOM |
| | AND MECHANICAL ROOM BENEATH THE ENCLOSED STAIR |
| | ENCLOSURE HAVING TO HAVE 1 HOUR FIRE RATING THE DOORS |
| | WILL ALSO NEED TO HAVE A FIRE RATING OPENING |
| | PROTECTIVES PER 2014 FBC-B TABLE 716.5. |
| | |
| | 6) PLEASE BE AWARE OF AN ERROR IN FBC-B TABLE 508.4 FOR |
| | FIRE RATINGS BETWEEN S1 AND S2 OCCUPANCIES. PLEASE |
| | REVIEW THE BUILDING OFFICIALS ASSOCIATION INFORMAL |
| | INTERPRETATION: |
| | DATE: TUE JUL 1 2014 |
| | REPORT: 7357 |
| | CODE: BUILDING CODE YEAR: 2010 |
| | SECTION: TABLE 508.4 |
| | QUESTION: |
| | IS IT THE INTENT OF TABLE 508.4 TO REQUIRE A (1HR (S), |
| | 2HR (NS)) SEPARATION BETWEEN B AND S-2 OCCUPANCY AND NO |
| | SEPARATION REQUIREMENT BETWEEN B AND S-1 OCCUPANCY? |
| | COMMENT: |
| | PER CHAPTER 3, S-2 OCCUPANCY ARE DEFINED AS LOW- HAZARD |
| | STORAGE, WHEREAS S-1 OCCUPANCY IS DEFINED AS |
| | MODERATE-HAZARD OCCUPANCY. THE STORED MATERIALS LIST |
| | FOR S-1 OCCUPANCY IS MUCH MORE HAZARDOUS THAN THE LIST |
| | FOR S-2 OCCUPANCY AND ONE WOULD THINK THAT THE S-1 |
| | OCCUPANCY WOULD REQUIRE THE SEPARATION AND THE S-2 |
| | OCCUPANCY WOULD NOT. |
| | ANSWER: |
| | BASED ON THE INFORMATION REVIEWED, IT APPEARS YOU ARE |
| | CORRECT THAT A TYPO EXISTS. THE BEST APPROACH FOR THIS |
| | PARTICULAR ISSUE WOULD BE EITHER A FORMAL |
| | INTERPRETATION WHICH HAS STANDING OR A DEC STATEMENT |
| | FROM THE FLORIDA BUILDING COMMISSION. PLEASE SEE THE |
| | COMMENTARY BELOW. |
| | COMMENTARY: |
| | TABLE 508.4 DOES APPEAR TO HAVE A TYPO. THE 2001 |
| | FLORIDA BUILDING CODE, TABLE 704.1 REQUIRED A 3 HOUR |
| | SEPARATION FOR S1 AND A 2 HOUR SEPARATION FOR S2. IN |
| | THE 2004 CODE TABLE 706.3.7 ALSO REQUIRES 3 HOURS FOR |
| | S1 AND 2 HOURS FOR S2. THE TYPO APPEARS TO HAVE BEEN |
| | INTRODUCED WITH TABLE 508.4 IN THE 2007 CODE. TABLE |
| | 508.4 APPEARS TO HAVE BEEN WRONG SINCE ITS INCEPTION. |
| | SUBMITTING A REQUEST FOR A FORMAL INTERPRETATION WOULD |
| | PERMIT APPLICATION OF CORRECTION TO THIS ISSUE UNTIL A |
| | CODE CHANGE CAN BE MADE, IF IT IS NOT ALREADY IN THE |
| | WORKS. |
| | NOTICE: |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN |
| | COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC, |
| | AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| | INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| | INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE. |
| | THIS INTERPRETATION IS INFORMAL, NON-BINDING AND |
| | SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| | BUILDING OFFICIAL. |
| | |
| | 7A) COMPLIED. SHEET A2.2 SHOWS ON THE 2ND FLOOR A |
| | WAREHOUSE, PLEASE PROVIDE THE DESIGN LIVE LOADS PER |
| | 2014 FBC-B TABLE 1607.1(31) STORAGE WAREHOUSES. |
| | |
| | 7B) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 106.1 LIVE LOADS |
| | POSTED. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR OR |
| | PORTION THEREOF OF A COMMERCIAL OR INDUSTRIAL BUILDING |
| | IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), |
| | SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY |
| | THE OWNER IN THAT PART OF EACH STORY IN WHICH THEY |
| | APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO |
| | REMOVE OR DEFACE SUCH NOTICES. |
| | |
| | 7C) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 106.2 ISSUANCE OF |
| | CERTIFICATE OF OCCUPANCY. A CERTIFICATE OF OCCUPANCY |
| | REQUIRED BY SECTION 111 SHALL NOT BE ISSUED UNTIL THE |
| | FLOOR LOAD SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN |
| | INSTALLED. |
| | |
| | 8A) SEMI-COMPLIED. THE PLANS INDICATE NEW EXTERIOR |
| | OPENINGS OF THE SHELL OF THE BUILDING. PLEASE PROVIDE |
| | COMPLIANCE WITH: 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | SUBMITTED: NOA 11-1101.03 TRULITE MEDIUM OUTSWING |
| | ENTRANCE DOOR NON-IMPACT. NOT LARGE MISSILE TESTED PLUS |
| | THE PLANS INDICATE A INSWING SET OF DOORS. |
| | REPUBLIC DOORS & FRAMES DL418 STEEL FLUSH DOORS |
| | SUBMITTAL NO FLORIDA APPROVAL OR NOA. |
| | |
| | (B) WINDOWS: COMPLIED. |
| | |
| | (C) PANEL WALLS: WALL LOUVERS: GREENHECK SUBMITTAL NO |
| | FLORIDA APPROVAL OR NOA. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS: IMPACT COLONIAL SHUTTERS SUBMITTAL NO |
| | FLORIDA APPROVAL OR NOA. |
| | (G) PRE-ENGINEERED A/C STANDS: PRECISION ALUMINUM |
| | PRODUCTS SUBMITTAL NO FLORIDA APPROVAL OR NOA. |
| | |
| | 8B) SEMI-COMPLIED. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) SHEET A3.3 VERSES S3.1 THERE IS A DISCREPANCY IN |
| | PLANS AS TO LOCATION OF THE ROOF TOP A/C STANDS : |
| | 9A) SHOWS A NEW ROOF TOP A/C STAND, PLEASE PROVIDE THE |
| | WIND DESIGN CRITERIA AND PRESSURES FOR THE REQUIRED |
| | ANCHORING OF THE A/C CONDENSER STAND TO THE ROOF. |
| | PLEASE INDICATE HOW THE STAND WILL BE ANCHORED TO THE |
| | ROOF FRAMING MEMBERS. TIE INTO THE MAIN WIND FORCE |
| | RESISTING SYSTEM. |
| | |
| | 9B) DISCREPANCY IN PLANS SEE A3.3 & S3.1. PLEASE |
| | PROVIDE DOCUMENTATION THERE IS A PARAPET OF SUFFICIENT |
| | HEIGHT OR CODE COMPLIANCE WITH FBC-B 1013.6 MECHANICAL |
| | EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 9C)COMPLIED 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS |
| | OR ELEVATED STRUCTURES. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |