2016-04-05 14:52:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010290
 ADD: 805 N. RAILROAD AVE.
 CONT: PALM BEACH CAST STONE
 TEL: 561-835-4085
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. APRIL 04/2016
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3)2ND REQUEST. THE STRUCTURAL SHEET 5.1 SHOWS NEW STEEL
 COLUMNS BEING WELDED TO AN EXISTING W20X BEAM AS WELL
 AS NEW STEEL COLUMNS BEING WELDED ON THE 2ND FLOOR TO
 THE EXISTING W20X BEAM. NORMALLY THIS WOULD REQUIRE A
 RESIDENT INSPECTOR FOR BOLTED AND WELDED CONNECTIONS.
 110.3.9 OTHER INSPECTIONS SERVICES7. FOR BUILDINGS AND
 STRUCTURES OF UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION, BOLTED AND WELDED CONNECTIONS. PLEASE
 CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD TO SEE
 IF HE WILL REQUIRE THE RESIDENT INSPECTOR OR IF A
 WELDING CERTIFICATE FROM THE ONSITE WELDER WILL SUFFICE
 AND THE USE OF CITY BUILDING INSPECTORS.
 KEN CONRAD TEL: 561-805-6666.
  
 4)SEMI-COMPLIED. PLEASE NOTE SHEETS A2.1 AND A2.2 THE
 1ST FLOOR PLAN AND 2ND FLOOR PLAN DO HAVE WALL
 IDENTIFICATION TAGS THIS REVIEW. ON BOTH FLOORS THERE
 IS AN OCCUPANCY SEPARATION WALL THAT SEPARATES THE
 BUSINESS OCCUPANCY FROM THE S1 OCCUPANCY. SHEET A201 &
 A202 SHOW MOST OF THE WALL WITH A 1 HOUR OCCUPANCY
 SEPARATION, ONLY THE NEW BATH WALL ON THE 2ND FLOOR
 SHOWS A 2 HOUR FIRE RATING. PLEASE ALSO NOTE THE
 OPENING PROTECTIVES IN THIS 2 HOUR WALL WILL BE
 REQUIRED TO BE 1 ? HOUR OPENING PROTECTIVES SEE TABLE
 716.5 OF THE 2014 FBC-B.
  
 THE OTHER ISSUE WITH THE RATED WALLS, THEY ARE ALL
 SHOWN AS NON-BEARING WALLS, THE STRUCTURAL SHEETS SHOW
 COLUMNS THAT DO NOT SHOW ON THE ARCHITECTURAL SHEETS.
 PLEASE ALSO NOTE THE STAIR MID-LANDING WILL NEED TO BE
 STRUCTURAL WITH BRACING TO TAKE THE LOADS ON THE
 STRINGERS SINCE THE WALLS THAT CREATE THE FIRE RATED
 WALLS ARE ALSO NON-LOADBEARING. THE PLANS ARE NOT CLEAR
 IN THIS AREA. ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 107.2.1.3.
  
 5A) SEMI ?COMPLIED, THERE IS A 2 HOUR OCCUPANCY WALL
 AND OPENING PROTECTIVES. SEE COMMENT # 6. SHEET A2.1
 SHOWS (2) ROOMS LOCATED BENEATH THE STAIRS, THE
 RESTROOM 102 AND THE MECHANICAL ROOM 103. NOT HAVING A
 WALL LEGEND THAT IDENTIFIES THE TYPE OF WALLS PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B;
 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS.
 THE WALLS CEILINGS AND SOFFITS WITHIN ENCLOSED USABLE
 SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 5B) SEMI ?COMPLIED, THERE IS A 2 HOUR OCCUPANCY WALL
 AND OPENING PROTECTIVES. SEE COMMENT # 6. THE BATHROOM
 AND MECHANICAL ROOM BENEATH THE ENCLOSED STAIR
 ENCLOSURE HAVING TO HAVE 1 HOUR FIRE RATING THE DOORS
 WILL ALSO NEED TO HAVE A FIRE RATING OPENING
 PROTECTIVES PER 2014 FBC-B TABLE 716.5.
  
 6) PLEASE BE AWARE OF AN ERROR IN FBC-B TABLE 508.4 FOR
 FIRE RATINGS BETWEEN S1 AND S2 OCCUPANCIES. PLEASE
 REVIEW THE BUILDING OFFICIALS ASSOCIATION INFORMAL
 INTERPRETATION:
 DATE: TUE JUL 1 2014
 REPORT: 7357
 CODE: BUILDING CODE YEAR: 2010
 SECTION: TABLE 508.4
 QUESTION:
 IS IT THE INTENT OF TABLE 508.4 TO REQUIRE A (1HR (S),
 2HR (NS)) SEPARATION BETWEEN B AND S-2 OCCUPANCY AND NO
 SEPARATION REQUIREMENT BETWEEN B AND S-1 OCCUPANCY?
 COMMENT:
 PER CHAPTER 3, S-2 OCCUPANCY ARE DEFINED AS LOW- HAZARD
 STORAGE, WHEREAS S-1 OCCUPANCY IS DEFINED AS
 MODERATE-HAZARD OCCUPANCY. THE STORED MATERIALS LIST
 FOR S-1 OCCUPANCY IS MUCH MORE HAZARDOUS THAN THE LIST
 FOR S-2 OCCUPANCY AND ONE WOULD THINK THAT THE S-1
 OCCUPANCY WOULD REQUIRE THE SEPARATION AND THE S-2
 OCCUPANCY WOULD NOT.
 ANSWER:
 BASED ON THE INFORMATION REVIEWED, IT APPEARS YOU ARE
 CORRECT THAT A TYPO EXISTS. THE BEST APPROACH FOR THIS
 PARTICULAR ISSUE WOULD BE EITHER A FORMAL
 INTERPRETATION WHICH HAS STANDING OR A DEC STATEMENT
 FROM THE FLORIDA BUILDING COMMISSION. PLEASE SEE THE
 COMMENTARY BELOW.
 COMMENTARY:
 TABLE 508.4 DOES APPEAR TO HAVE A TYPO. THE 2001
 FLORIDA BUILDING CODE, TABLE 704.1 REQUIRED A 3 HOUR
 SEPARATION FOR S1 AND A 2 HOUR SEPARATION FOR S2. IN
 THE 2004 CODE TABLE 706.3.7 ALSO REQUIRES 3 HOURS FOR
 S1 AND 2 HOURS FOR S2. THE TYPO APPEARS TO HAVE BEEN
 INTRODUCED WITH TABLE 508.4 IN THE 2007 CODE. TABLE
 508.4 APPEARS TO HAVE BEEN WRONG SINCE ITS INCEPTION.
 SUBMITTING A REQUEST FOR A FORMAL INTERPRETATION WOULD
 PERMIT APPLICATION OF CORRECTION TO THIS ISSUE UNTIL A
 CODE CHANGE CAN BE MADE, IF IT IS NOT ALREADY IN THE
 WORKS.
 NOTICE:
 THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN
 COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC,
 AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS
 INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE
 INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE.
 THIS INTERPRETATION IS INFORMAL, NON-BINDING AND
 SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL
 BUILDING OFFICIAL.
  
 7A) COMPLIED. SHEET A2.2 SHOWS ON THE 2ND FLOOR A
 WAREHOUSE, PLEASE PROVIDE THE DESIGN LIVE LOADS PER
 2014 FBC-B TABLE 1607.1(31) STORAGE WAREHOUSES.
  
 7B) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 106.1 LIVE LOADS
 POSTED. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR OR
 PORTION THEREOF OF A COMMERCIAL OR INDUSTRIAL BUILDING
 IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40 KN/M2),
 SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY
 THE OWNER IN THAT PART OF EACH STORY IN WHICH THEY
 APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO
 REMOVE OR DEFACE SUCH NOTICES.
  
 7C) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 106.2 ISSUANCE OF
 CERTIFICATE OF OCCUPANCY. A CERTIFICATE OF OCCUPANCY
 REQUIRED BY SECTION 111 SHALL NOT BE ISSUED UNTIL THE
 FLOOR LOAD SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN
 INSTALLED.
  
 8A) SEMI-COMPLIED. THE PLANS INDICATE NEW EXTERIOR
 OPENINGS OF THE SHELL OF THE BUILDING. PLEASE PROVIDE
 COMPLIANCE WITH: 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 SUBMITTED: NOA 11-1101.03 TRULITE MEDIUM OUTSWING
 ENTRANCE DOOR NON-IMPACT. NOT LARGE MISSILE TESTED PLUS
 THE PLANS INDICATE A INSWING SET OF DOORS.
 REPUBLIC DOORS & FRAMES DL418 STEEL FLUSH DOORS
 SUBMITTAL NO FLORIDA APPROVAL OR NOA.
  
 (B) WINDOWS: COMPLIED.
  
 (C) PANEL WALLS: WALL LOUVERS: GREENHECK SUBMITTAL NO
 FLORIDA APPROVAL OR NOA.
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS: IMPACT COLONIAL SHUTTERS SUBMITTAL NO
 FLORIDA APPROVAL OR NOA.
 (G) PRE-ENGINEERED A/C STANDS: PRECISION ALUMINUM
 PRODUCTS SUBMITTAL NO FLORIDA APPROVAL OR NOA.
  
 8B) SEMI-COMPLIED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) SHEET A3.3 VERSES S3.1 THERE IS A DISCREPANCY IN
 PLANS AS TO LOCATION OF THE ROOF TOP A/C STANDS :
 9A) SHOWS A NEW ROOF TOP A/C STAND, PLEASE PROVIDE THE
 WIND DESIGN CRITERIA AND PRESSURES FOR THE REQUIRED
 ANCHORING OF THE A/C CONDENSER STAND TO THE ROOF.
 PLEASE INDICATE HOW THE STAND WILL BE ANCHORED TO THE
 ROOF FRAMING MEMBERS. TIE INTO THE MAIN WIND FORCE
 RESISTING SYSTEM.
  
 9B) DISCREPANCY IN PLANS SEE A3.3 & S3.1. PLEASE
 PROVIDE DOCUMENTATION THERE IS A PARAPET OF SUFFICIENT
 HEIGHT OR CODE COMPLIANCE WITH FBC-B 1013.6 MECHANICAL
 EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 9C)COMPLIED 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  