Plan Review Notes
Plan Review Notes For Permit 16010290
Permit Number 16010290
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-26 10:27:221) THE BREAK ROOM SINK ON THE SECOND FLOOR SHALL COMPLY
 WITH 2014 FBC-ACCESS. SEC.212 & 606.
 2) INDICATE ON THE PLANS IF THE OCCUPANT LOAD OF THIS
 SPACE IS BEING INCREASED OR REMAINING THE SAME. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) THE SHOWER IN THE PRIVATE OFFICE BATHROOM SHALL BE A
 MINIMUM OF 36 INCHES WIDE.2014 FBCA SECS.213.2,
 213.3.6, & 608, 608.2.3.
 4) THE SHOWER CONTROLS SHALL COMPLY WITH 2014 FBCA SEC.
 608.5.2.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE HUB DRAIN FOR THE ELEVATOR SUMP SYSTEM SHALL BE
 EQUIPPED WITH A TRAP PRIMER. 2014 FPC SEC. 1002.4.
 7) THE WATER SUPPLY TO THE WATER HEATER IS SHOWN AS
 1/2" ON THE WATER RISER. CLARIFY.
 8) A SERVICE SINK IS REQUIRED IN STORAGE & BUSINESS
 OCCUPANCIES PER 2014 FPC TABLE 403.1. IF THERE IS ONE
 EXISTING , SHOW THE LOCATION ON THE PLAN.
 9) A DRINKING FOUNTAIN( MIN. OF 2 PER THE ACCESSIBILITY
 CODE) IS REQUIRED PER 2014 FPC TABLE 403.1. IF THERE
 ARE TWO EXISTING , SHOW THE LOCATION ON THE PLAN.
 10) THE SECOND FLOOR BATHROOM SHALL COMPLY WITH THE
 2014 FBCA SEC.213.2 & 603 FOR SIZE, FIXTURE CLEARANCES,
 CLEAR FLOOR SPACE FOR FIXTURES,ETC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  