2016-01-15 16:27:201ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010290
 01/15/16
  
 1) THE AC SYSTEM SIZING CALCULATIONS ARE INDICATING
 INCORRECT CLIMATE DATA FROM MIAMI: PLEASE PROVIDE WEST
 PALM BEACH AS THE LOCATION AND SOURCE OF CLIMATE DATA.
 2) THE ENERGY FORM 506-2014 IS INDICATING CAPACITIES
 FOR AHU-1 & 2 THAT DIFFER FROM THE CAPACITIES ON THE AC
 SCHEDULE- SHEET M0-1.
 3) SHEET M1.2: THE O/A DUCT FOR AHU-1 APPEARS TO BE
 PENETRATING THE EXIT STAIRWAY CEILING AND FLOOR WHICH
 IS PROHIBITIED BY SECTION 1022.5 FBC-14 BUILDING. IF
 THE THE DUCT IS TO REMAIN IN THE STAIRWAY IT MUST BE IN
 A FIRE-RATED ENCLOSURE, AND A DAMPER IS REQUIRED AT THE
 FIRE-RATED CEILING.
 4) THE AC CLOSET DOOR #209 SHALL BE NON-COMBUSTIBLE-
 SEE SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION.
 5) M1.1: THE RETURN AIR TRANSFER DUCT SHALL BE SIZED
 1.5 TIMES THE CROSS-SECTIONAL AREAS OF THE SUPPLYU
 DUCTS ENTERING THE ROOM OR 252 SQ. INCHES. SEE SECTION
 601.5 FBC-14 MECHANICAL AND INCREASE THE SIZE OF THE
 DUCT ACCORDINGLY.
 6) PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLIES FOR ALL REFRIGERANT AND CONDENSATE PIPINGS,
 AND DUCTS ETC. PENETRATING FIRE-RATED WALLS.
 7) M0.2: PLEASE PROVIDE THE WIND LOAD DESIGN CRITERIA
 (BASIC WIND SPEED AND CONVERSION, EXPOSURE CATEGORY,
 IMPORTANCE FACTOR, HEIGHT AND EXPOSURE COEFFICIENT
 ETC.) USED TO ESTABLISH THE CU TO ROOF STAND ATTACHMENT
 DETAILS- SEE SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  