| 2016-01-15 16:27:20 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16010290 |
| | 01/15/16 |
| | |
| | 1) THE AC SYSTEM SIZING CALCULATIONS ARE INDICATING |
| | INCORRECT CLIMATE DATA FROM MIAMI: PLEASE PROVIDE WEST |
| | PALM BEACH AS THE LOCATION AND SOURCE OF CLIMATE DATA. |
| | 2) THE ENERGY FORM 506-2014 IS INDICATING CAPACITIES |
| | FOR AHU-1 & 2 THAT DIFFER FROM THE CAPACITIES ON THE AC |
| | SCHEDULE- SHEET M0-1. |
| | 3) SHEET M1.2: THE O/A DUCT FOR AHU-1 APPEARS TO BE |
| | PENETRATING THE EXIT STAIRWAY CEILING AND FLOOR WHICH |
| | IS PROHIBITIED BY SECTION 1022.5 FBC-14 BUILDING. IF |
| | THE THE DUCT IS TO REMAIN IN THE STAIRWAY IT MUST BE IN |
| | A FIRE-RATED ENCLOSURE, AND A DAMPER IS REQUIRED AT THE |
| | FIRE-RATED CEILING. |
| | 4) THE AC CLOSET DOOR #209 SHALL BE NON-COMBUSTIBLE- |
| | SEE SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. |
| | 5) M1.1: THE RETURN AIR TRANSFER DUCT SHALL BE SIZED |
| | 1.5 TIMES THE CROSS-SECTIONAL AREAS OF THE SUPPLYU |
| | DUCTS ENTERING THE ROOM OR 252 SQ. INCHES. SEE SECTION |
| | 601.5 FBC-14 MECHANICAL AND INCREASE THE SIZE OF THE |
| | DUCT ACCORDINGLY. |
| | 6) PROVIDE UL TESTED AND APPROVED FIRESTOPPING |
| | ASSEMBLIES FOR ALL REFRIGERANT AND CONDENSATE PIPINGS, |
| | AND DUCTS ETC. PENETRATING FIRE-RATED WALLS. |
| | 7) M0.2: PLEASE PROVIDE THE WIND LOAD DESIGN CRITERIA |
| | (BASIC WIND SPEED AND CONVERSION, EXPOSURE CATEGORY, |
| | IMPORTANCE FACTOR, HEIGHT AND EXPOSURE COEFFICIENT |
| | ETC.) USED TO ESTABLISH THE CU TO ROOF STAND ATTACHMENT |
| | DETAILS- SEE SECTION 1609 FBC-14 BUILDING. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |