| 2016-01-25 12:41:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET A 5.3 - PROVIDE HEIGHT DIMENSION ON STAIRWAY |
| | LANDING COMPLYING WITH NFPA 101, CHAPTER 7, TABLE |
| | 7.2.2.2.2.1.1, - MINIMUM HEADROOM - 6'8" |
| | |
| | 2. SHEET A 6.1 - PROVIDE EXIT HARDWARE FOR ALL EXITS |
| | DOORS COMPLYING WITH NFPA 101, CHAPTER 7. |
| | |
| | 3. SHEET A 5.3 - PROVIDE THE REQUIRED 1 HOUR FIRE |
| | RATING SEPARATION UNDER THE EXIT STAIRS PER NFPA 101, |
| | CHAPTER 7, 7.1.3.2 |
| | |
| | 4. SHEET A 2.1 - PROVIDE INDICATIONS THAT ELEVATOR |
| | INSTALLATION SHALL COMPLY WITH NFPA 101, CHAPTER 9, |
| | 9.4.3 FIRE FIGHTER?S EMERGENCY OPERATIONS. |
| | 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. |
| | |
| | 5. SHEET A 4.1- PER FLORIDA 69A-60.0081; NOTICE SIGNAGE |
| | IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |