2016-01-25 12:41:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A 5.3 - PROVIDE HEIGHT DIMENSION ON STAIRWAY
 LANDING COMPLYING WITH NFPA 101, CHAPTER 7, TABLE
 7.2.2.2.2.1.1, - MINIMUM HEADROOM - 6'8"
  
 2. SHEET A 6.1 - PROVIDE EXIT HARDWARE FOR ALL EXITS
 DOORS COMPLYING WITH NFPA 101, CHAPTER 7.
  
 3. SHEET A 5.3 - PROVIDE THE REQUIRED 1 HOUR FIRE
 RATING SEPARATION UNDER THE EXIT STAIRS PER NFPA 101,
 CHAPTER 7, 7.1.3.2
  
 4. SHEET A 2.1 - PROVIDE INDICATIONS THAT ELEVATOR
 INSTALLATION SHALL COMPLY WITH NFPA 101, CHAPTER 9,
 9.4.3 FIRE FIGHTER?S EMERGENCY OPERATIONS.
 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 5. SHEET A 4.1- PER FLORIDA 69A-60.0081; NOTICE SIGNAGE
 IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
  