| Plan Review Notes For Permit 16010287 |
| Permit Number |
16010287 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-28 14:39:30 | 1ST ELECTRICAL REVIEW NOTES: | | | REVIEWED FOR COMPLIANCE WITH: | | | FBC 5TH EDITION 2014 | | | NFPA 70 2011 (NEC) | | | | | | CORRECTIONS REQUIRED: | | | 1. ACCORDING TO THE MANUFACTURER?S SPECS THIS UNIT HAS | | | A 125 AMP PANEL, (ASSUMED TO BE 120/240 VAC 1? | | | SERVICE), THE REQUIRED EXTERNAL LIGHT AND GFCI | | | PROTECTED OUTLET. | | | 2. YOU NEED TO SUBMIT AN ELECTRICAL RISER DIAGRAM AS | | | REQUIRED BY NEC 215.5. THIS DIAGRAM MUST INCLUDE | | | CONDUCTOR SIZING AND TYPE. THE CONDUCTORS MUST BE SIZED | | | TO SO AS NOT TO PERMIT GREATER THAN 3% VOLTAGE DROP. | | | 3. YOU NEED TO MARK ON THE SITE PLAN THE LOCATION OF | | | THE POWER SOURCE FOR THE UNIT. | | | 4. IF A SERVICE RACK IS GOING TO BE ERECTED, PROTECTION | | | FROM PHYSICAL DAMAGE MUST BE PROVIDED. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|