Plan Review Notes
Plan Review Notes For Permit 16010287
Permit Number 16010287
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-28 14:39:301ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. ACCORDING TO THE MANUFACTURER?S SPECS THIS UNIT HAS
 A 125 AMP PANEL, (ASSUMED TO BE 120/240 VAC 1?
 SERVICE), THE REQUIRED EXTERNAL LIGHT AND GFCI
 PROTECTED OUTLET.
 2. YOU NEED TO SUBMIT AN ELECTRICAL RISER DIAGRAM AS
 REQUIRED BY NEC 215.5. THIS DIAGRAM MUST INCLUDE
 CONDUCTOR SIZING AND TYPE. THE CONDUCTORS MUST BE SIZED
 TO SO AS NOT TO PERMIT GREATER THAN 3% VOLTAGE DROP.
 3. YOU NEED TO MARK ON THE SITE PLAN THE LOCATION OF
 THE POWER SOURCE FOR THE UNIT.
 4. IF A SERVICE RACK IS GOING TO BE ERECTED, PROTECTION
 FROM PHYSICAL DAMAGE MUST BE PROVIDED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  