| Plan Review Notes For Permit 16010266 |
| Permit Number |
16010266 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-25 14:23:17 | 1ST REVIEW: FBC 2014 MECHANICAL | | | REVISION PERMIT #16010266 | | | 2/25/16 | | | | | | 1) PLEASE REMOVE THE SUBMITTAL FOR THE ROOF-MOUNTED | | | TURBINE FANS- THEY ARE DESIGNED FOR INSTALLATION ON | | | SLOPED SHINGLE ROOFS. PLEASE NOTE THAT REVISION | | | #16020897 WAS APPROVED TODAY FOR THE SAME PROJECT WITH | | | A REVISED M01.01 PLAN SHEET AND SUBMITTAL FOR GRAVITY | | | VENTILATORS TO REPLACE THE TURBINES. | | | 2) COMPLY WITH BUILDING REVIEW COMMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|