2016-02-25 10:07:23BUILDING PLAN REVIEW
 W. P. B. REVISION: 16010266
 W. P. B. PERMIT: 15080631
 ADD: 7320 S. DIXIE HWY
 CONT: CAL DEVELOPMENT
 TEL: (954)564-0655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. FEB. 25/ 2016
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1) SUBMITTALS AND REVISIONS SUBMITTED: HAVE A NPJ
 TECHNICAL SERVICES ON THE TOP OF ALL THE SUBMITTALS,
 PLEASE IDENTIFY WHAT YOUR RELATIONSHIP IS WITH THIS
 PROJECT. YOU ARE NOT THE ARCHITECT OF RECORD (DANA
 MULLER AR 92911) NOR THE MECHANICAL ENGINEER NISIT
 SAPPARKHAO NOR THE CONTRACTOR CAL DEVELOPMENT.
 ALL SUBMITTALS ARETO BE REVIEWED BY THE DESIGNER OF
 RECORD (ARCHITECT) FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
  
 THE SECOND ISSUE IS THE SUBMITTAL ONLY LIST ALUMINUM
 HANDRAIL MODIFICATIONS WITHIN THIS PACKAGE THERE IS:
 A) STAIR TREAD MODIFICATION AS WELL AS HANDRAIL
 MODIFICATIONS THOMAS J. TWOMEY P.E.
 B) EXTERIOR LOUVERS NOA10-0920.16 SIZED TO LESS THAN ?
 OF THE 8X11 SHEET. NOT READABLE FOR RECORD RETENTION.
 C) CEILING AND WALL A/C GRILLS
 D) FIRE DAMPERS
 E) DC-CSSF-NN WELDED ROOF CURB
 F) NOA 14-1224.14 GAF MASTER FLOW GALVANIZED WIND
 TURBINE
  
 1A) 2ND REQUEST. ROOF CURBS : MODEL DC-CSSF-NN
 MANUFACTURERS CUT SHEET INDICATES THEY HAVE MIAMI-DADE
 NOA'S, LISTED ON CUT SHEET. THERE IS NO ENGINEERS
 SIGNATURE AND SEAL ASSOCIATED WITH THIS SHEET ALTHOUGH
 THERE ARE TIE DOWN DIRECTIONS FOR VARIOUS TYPES OF ROOF
 DECKS, NOR IS THERE A WIND DESIGN CRITERIA INDICATING
 TO WHAT WIND DESIGN THIS WAS TESTED. ALSO PROVIDE THE
 MEAN ROOF HEIGHT OF THE BUILDING, NOTE THIS IS A 3
 STORY BUILDING WITH WOOD FLOOR AND ROOF TRUSSES WITH A
 DRIVE THRU ON THE 1ST FLOOR.
  
 PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
  
 1B) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND OR EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 1C) 2ND REQUEST. THE MECHANICAL SHEET M01.01 DOES SHOW
 THE USE OF THE 12 INCH GALVANIZED WIND TURBINE
 INSTALLED ON A ROOF TOP STAND. THIS SAME DETAIL SHOWS
 THE TURBINE WITH A LIPPED VERTICAL EDGE TO ATTACH THE
 TURBINE TO THE BASE. NOTE THE TURBINE DOES NOT COME
 WITH THIS LIPPED EDGE, LIMITATION NOTE 3 THIS TURBINE
 IS TO BE USED ON SLOPED ROOFS, WITH WOOD DECKS.
 THE OTHER ISSUE IS IN LIMITATION # 4 ONLY ALLOWS THE
 USE OF HIS PRODUCT TO 33 FEET ABOVE GRADE!!!!!!!!
  
 THE NOA SUBMITTED 14-1224.14 GAF MASTER FLOW 12 INCH
 GALVANIZED WIND TURBINE, PLEASE REVIEW PAGE 4 OF 5,
 UNDER THE HEADING OF LIMITATIONS: NOTE # 3. THIS
 ACCEPTANCE IS FOR INSTALLATION WITH ASPHALT SHINGLE
 ROOF SYSTEMS ONLY. NOTE # 4 LIMITATION, VENT NOT TO BE
 INSTALLED ON ROOF MEAN HEIGHT GREATER THAN 33 FEET.
  
 1D) 2ND REQUEST. ALUMINUM HANDRAIL/ GUARDRAIL SYSTEM
 SUBMITTAL, SEE SHEET A00.30 DETAIL #4 NOTE # 1.
 CONTRACTOR TO PROVIDE SIGNED AND SEALED SHOP DRAWINGS
 AND CALCULATIONS OF THE GUARDRAIL DESIGN TO THE
 ARCHITECT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 1E) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  