2016-01-13 17:37:26 
 BUILDING PLAN REVIEW
 W. P. B. REVISION: 16010266
 W. P. B. PERMIT: 15080631
 ADD: 7320 S. DIXIE HWY
 CONT: CAL DEVELOPMENT
 TEL: (954)564-0655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 13/ 2016
 ACTION: DENIED
  
 1) SUBMITTALS AND REVISIONS SUBMITTED;
  
 1A) ROOF CURBS : MODEL DC-CSSF-NN MANUFACTURERS CUT
 SHEET INDICATES THEY HAVE MIAMI-DADE NOA'S, LISTED ON
 CUT SHEET. PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
  
 1B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND OR EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 1C) THE NOA SUBMITTED 14-1224.1.4 GAF MASTER FLOW 12
 INCH GALVANIZED WIND TURBINE, PLEASE REVIEW PAGE 4 OF
 5, UNDER THE HEADING OF LIMITATIONS: NOTE # 3. THIS
 ACCEPTANCE IS FOR INSTALLATION WITH ASPHALT SHINGLE
 ROOF SYSTEMS ONLY. NOTE # 4 LIMITATION, VENT NOT TO BE
 INSTALLED ON ROOF MEAN HEIGHT GREATER THAN 33 FEET.
  
 1D) ALUMINUM HANDRAIL/ GUARDRAIL SYSTEM SUBMITTAL, SEE
 SHEET A00.30 DETAIL #4 NOTE # 1. CONTRACTOR TO PROVIDE
 SIGNED AND SEALED SHOP DRAWINGS AND CALCULATIONS OF THE
 GUARDRAIL DESIGN TO THE ARCHITECT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 1E) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER