| 2018-03-29 12:25:03 | NEW SINGLE FAMILY RESIDENCE (R3) SIXTH MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| | ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| | IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 1- IT LOOKS LIKE THE EQUIPMENT MAY BE OVERSIZED AGAIN. |
| | IT LOOKS LIKE THE EQUIPMENT WAS SIZED BASED ON A LARGE |
| | NUMBER OF PEOPLE. 35 PEOPLE IS A LARGE QUANTITY FOR A |
| | SINGLE FAMILY RESIDENCE. EQUIPMENT CAN NOT BE SIZED |
| | BASED ON OTHER FACTORS THAT MAY AFFECT THE EQUIPMENT |
| | SIZING. REVISE CALCULATIONS AS REQUIRED TO MATCH ACTUAL |
| | DESIGN CONDITIONS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION. NOTE: COORDINATE DRAWING M.1 WITH REVISED |
| | EQUIPMENT SIZING CALCULATIONS. |
| | |
| | |
| | 2- EQUIPMENT SHOWN ON A/C PLAN DOESN'T MATCH EQUIPMENT |
| | SHOWN ON THE AHRI CERTIFICATES SUBMITTED. REVISE AS |
| | REQUIRED TO MATCH. NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T |
| | STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR |
| | REFERENCE. |
| | |