| 2016-05-05 14:40:20 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY |
| | SEC. R401.4 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| | (REPEAT COMMENT. NOT ADDRESSED. NEED REPORT TO VERIFY |
| | PROPOSED DESIGN AND SOIL PREPARATION RECOMMENDATIONS.). |
| | |
| | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| | R401.3 OF FBC RESIDENTIAL, 5TH EDITION (2014). (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED; |
| | (NOTE: ENGINEER MAY BE CHARGED 4 TIMES THE PLAN REVIEW |
| | FEES AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) EACH |
| | TIME AFTER THE THIRD REVIEW IF THE PLANS ARE DENIED) |
| | |
| | A) TYPE OF ADJACENT WALL SHOWN ON ITEM #9 IS INCORRECT. |
| | SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT |
| | COMMENT. NOTE: REVISE TYPE OF WALL AND INSULATION |
| | R-VALUE. SEE PLANS). |
| | |
| | B) PAGE 3 OF 5: WHERE IS THE NORTH INSULATED DOOR ON |
| | THE SECOND FLOOR SHOWN ON PLANS. THERE ARE NO INSULATED |
| | DOORS ON SECOND FLOOR. SEE PLANS AND PRODUCT APPROVALS |
| | AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT). |
| | |
| | C) WALLS INFORMATION ON PAGE 3 OF 5 FOR THE GARAGE WALL |
| | IS INCORRECT. REVISE THE WALL ORIENTATION AND WALL |
| | TYPE. SEE PLANS AND REVISE AS REQUIRED. THERE ARE NO |
| | GARAGE STEEL WALLS ON THE SECOND FLOOR. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). (REPEAT COMMENT). |
| | |
| | D) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT). |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| | WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT |
| | USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 4- SUBMITTAL PACKAGE IS MISSING ONE SET OF PRODUCT |
| | APPROVALS. PROVIDE THE SECOND SET. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T |
| | STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR |
| | REFERENCE. |
| | |