| 2016-02-18 13:41:57 | 1- ENGINEER OF RECORD TO SPECIFY THE METAL ROOF | | | FASTENING FOR ALL ROOF ZONES AS REQUIRED BY SEC. | | | 107.2.1.2 OF CITY AMENDMENTS. | | | NOTE: CLEARLY IDENTIFY APPROVED ASSEMBLY ON METAL ROOF | | | NOA 13-0114.03 SUBMITTED TO VERIFY COMPLIANCE WITH THE | | | CALCULATED DESIGN PRESSURES. ALSO, SEE LIMITATION #2 ON | | | PAGE 7 OF 9 OF NOA SUBMITTED. COORDINATE WITH REVISED | | | DESIGN PRESSURES REQUIRED BY ITEM #2 ABOVE. | | | |
|