| Plan Review Notes For Permit 16010225 |
| Permit Number |
16010225 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-18 13:47:45 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: | | | ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE HIS | | | NAME AND ALL HIS INFORMATION AND TO PROVIDE ORIGINAL | | | SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. | | | | | | 2- MECHANICAL PLAN M.1 SUBMITTED; | | | A) SIZE OF "TRANSFER DUCTS" SHOWN ON THE SECOND FLOOR | | | BEDROOMS DON'T COMPLY WITH THE BALANCED RETURN AIR SEC. | | | M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). SHOW | | | COMPLIANCE. | | | | | | B) CLARIFY HOW THE RETURN AREA GRILLS SHOWN ON THE | | | FIRST FLOOR BY THE DINING AREA AND ON THE SECOND FLOOR | | | BY THE ATTIC ACCESS ARE CONNECTED TO THE AIR HANDLER | | | UNIT. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T | | | STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR | | | REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|