| Plan Review Notes For Permit 16010210 |
| Permit Number |
16010210 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-10 16:11:39 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010210 | | | 3/10/16 | | | | | | 1) PLEASE REFER TO TABLE 403.3 FBC-14 MECHANICAL, AND | | | SEE TOILET ROOMS- PUBLIC AND FOOTNOTE E: 50 CFM EXHAUST | | | AIRFLOW RATE REQUIRED FOR EACH TOILET OR URINAL. THE | | | EXHAUST FAN SCHEDULE ON SHEET M-1 INDICATES THE CFM | | | CAPACITIES OF THE FANS ARE INADEQUATE: A) WORK AREA 1 | | | REQUIRES MINIMUM 300 CFM'S OF EXHAUST. B) WORK AREA 2 | | | REQUIRES 400 CFM'S OF EXHAUST. C) WORK AREA 3 REQUIRES | | | 100 CFM'S OF EXHAUST. | | | 2) M-1: PLEASE CLARIFY WHY OUTDOOR AIR CALCULATIONS ARE | | | SHOWN FOR LAUNDRY AREAS: THERE ARE NO LAUNDRIES SHOWN | | | ON THE PLAN. IF LAUNDRY IS TO BE INCLUDED UNDER THIS | | | PERMIT, PROVIDE COMPLETE PLANS AND SPECIFICATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|