Plan Review Notes
Plan Review Notes For Permit 16010210
Permit Number 16010210
Review Stop M
Sequence Number 2
Notes
Date Text
2016-03-10 16:11:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010210
 3/10/16
  
 1) PLEASE REFER TO TABLE 403.3 FBC-14 MECHANICAL, AND
 SEE TOILET ROOMS- PUBLIC AND FOOTNOTE E: 50 CFM EXHAUST
 AIRFLOW RATE REQUIRED FOR EACH TOILET OR URINAL. THE
 EXHAUST FAN SCHEDULE ON SHEET M-1 INDICATES THE CFM
 CAPACITIES OF THE FANS ARE INADEQUATE: A) WORK AREA 1
 REQUIRES MINIMUM 300 CFM'S OF EXHAUST. B) WORK AREA 2
 REQUIRES 400 CFM'S OF EXHAUST. C) WORK AREA 3 REQUIRES
 100 CFM'S OF EXHAUST.
 2) M-1: PLEASE CLARIFY WHY OUTDOOR AIR CALCULATIONS ARE
 SHOWN FOR LAUNDRY AREAS: THERE ARE NO LAUNDRIES SHOWN
 ON THE PLAN. IF LAUNDRY IS TO BE INCLUDED UNDER THIS
 PERMIT, PROVIDE COMPLETE PLANS AND SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  