Plan Review Notes
Plan Review Notes For Permit 16010210
Permit Number 16010210
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-19 05:32:041) INDICATE THE LEVEL OF ALTERATION ON THE PLANS PER
 THE 2014 FBC-EXISTING, SEC. 301.1.
 2) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER THE
 2014 FBC SEC. 301, 302.
 3) SHT. A-1 - PROPOSED WORK AREA #1 IS CALLED OUT AS A
 MEN'S RESTROOM BUT A-3 NOTES THIS AS A WOMEN'S RESTROOM
 ON THE PLAN VIEW.THE SAME DISCREPANCY OCCURS FOR WORK
 AREA #2. CLARIFY.
 4) SUBMIT THE OCCUPANT LOAD OF THIS BUILDING TO ENSURE
 THERE WILL NOT BE ANY PLUMBING CODE VIOLATIONS DUE TO
 THE CHANGES IN THE TYPES AND AMOUNT OF PLUMBING
 FIXTURES.WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. A-2 - WORK AREA 3 - MEN'S RESTROOM - CLARIFY
 THE SCOPE OF WORK BEING DONE IN THIS RESTROOM. THE
 PLANS STATE "ENLARGE MEN'S RESTROOM BUT THE LAYOUT
 APPEARS UNCHANGED.
 6) SHT. P-1 - FIXTURE SCHEDULE NOTE #1 - THE WORK SHALL
 COMPLY WITH THE 2014 FBC, NOT THE 2010. 2014
 FBC-EXISTING SEC.801.3.
 7) SHT. P-1 - FIXTURE SCHEDULE NOTE #2 - THE MAXIMUM
 TEMPERATURE AT THE FIXTURE OUTLET SHALL BE 110 DEGREES.
 FBC-PLUMBING SEC.607.1.2.
 8) SHT. P-1 - WORK AREAS #1, 2, 3, 4 - THE PLANS SHOW
 EXISTING 3/4" CW & 1/2" CW. THIS IS OBVIOUSLY AN ERROR.
 PLEASE CORRECT.
 9) A SANITARY AND WATER RISER IS REQUIRED FOR ALL THE
 CHANGES BEING MADE TO THE SANITARY AND WATER SYSTEMS.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR