| Plan Review Notes For Permit 16010210 |
| Permit Number |
16010210 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-10 14:56:36 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE ADD A NOTE TO DRAWINGS INDICATING THAT NO NEW | | | LOADS ARE BEING ADDED UNDER THE SCOPE OF WORK. A NOTE | | | WILL SUFFICE. FBC 107 MINIMUM PLAN REVIEW CRITERIA | | | 2. DELETE FROM GENERAL NOTES NON-APPLICABLE ITEMS SUCH | | | AS THOSE THAT APPLY TO DWELLINGS OCCUPANCIES. FBC 107 | | | MINIMUM PLAN REVIEW CRITERIA | | | 3. SHOW ON PLANS THE EXISTING PANEL BOARD WHERE THE | | | EXISTING CIRCUITS ORIGINATE, TO THE RESTROOMS AREAS. NO | | | LOAD CALCULATIONS ARE REQUIRED DUE TO NO LOADS BEING | | | ALTERED. FBC 107 MINIMUM PLAN REVIEW CRITERIA | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|