| 2016-01-15 07:59:00 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010207 |
| | ADD: 4047 OKEECHOBEE BLVD SUITE # 126 |
| | CONT: THE AREA GROUP CBC050008/ FL0131 |
| | TEL: 561-603-4531 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 15/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE DESIGNER OF RECORD FOR THE DRAWINGS HAS NOT |
| | TAKEN OWNERSHIP OF THE PLANS, THEY NEED TO PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | 2) IT WOULD APPEAR WHOEVER DREW THE SUBMITTED PLANS IS |
| | LICENSED AS A ELECTRICAL CONTRACTOR AS WELL AS EITHER A |
| | CGC, OR A CBC SINCE BOTH TRADES ARE SHOWN ON THE PLANS. |
| | A CONTRACTOR CAN ONLY DRAW PLANS FOR THE TRADE THEY ARE |
| | LICENSED IN UNDER THE DOLLAR AMOUNT OF $125,000.00 AND |
| | (ELEC) (B) COMMERCIAL 800 AMPERES OR LESS. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 105.3.1.2. |
| | |
| | 3) THE PERMIT PLANS ARE DEFICIENT, THE DESIGNER OF |
| | RECORD DOES NOT INCLUDE WITH THE SUB-DIVIDING OF A |
| | TENANT SPACE, WHAT IS THE OCCUPANCY, FOR BOTH TENANT |
| | SPACES. THE DESIGNER OF RECORD HAS NOT MADE IT CLEAR TO |
| | WHICH TENANT SPACE THE PERMIT IS FOR SINCE THE TENANT |
| | SEPARATION WALL SHOWS ELECTRICAL FOR BOTH TENANT |
| | SPACES, AND DRYWALL WORK FOR BOTH TENANT SPACES BUT |
| | ONLY LIST WORK FOR UNIT 126.2014 FLORIDA BUILDING CODE |
| | W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) THE PERMIT PLANS ARE DEFICIENT, THE DESIGNER OF |
| | RECORD DOES NOT INCLUDE: |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1.1. COMMERCIAL BUILDINGS: |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | FIRE SPRIKLERS OR NOT REQUIRED? |
| | LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | ACCESSIBLE ROUTE |
| | TOILET FACILITIES |
| | DRINKING FOUNTAINS |
| | |
| | 5) THE PLAN STATES THE TENANT SEPARATION WALL IS A NEW |
| | WALL BUT DOES NOT PROVIDE ACUT SECTION THROUGH THE WALL |
| | INDICATING THE WALL HEIGHT, IF THE DESIGNER IS |
| | REQUIRING THE WALL TO BE FIRE RATED, TYPE OF CONNECTION |
| | TO THE TOP OF THE WALL. 708.3 FIRE-RESISTANCE RATING. |
| | FIRE PARTITIONS SHALL HAVE A FIRERESISTANCE RATING OF |
| | NOT LESS THAN 1 HOUR. |
| | |
| | 6) THE DESIGNER OF RECORD ALSO NEEDS TO SHOW COMPLIANCE |
| | OF HOW THEY ARE GOING TO ACHIEVE CODE COMPLIANCE WITH |
| | 2014 FBC-B 1607.14 INTERIOR WALLS AND PARTITIONS THAT |
| | EXCEED 6 FEET (1829 MM) IN HEIGHT, INCLUDING THEIR |
| | FINISH MATERIALS, SHALL HAVE ADEQUATE STRENGTH TO |
| | RESIST THE LOADS TO WHICH THEY ARE SUBJECTED. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |