Date Text
2016-02-18 08:40:46 
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
  
  
  
  
  
  
 (1). AAV ARE NOT ALLOWED BELOW THE FORTH FLOOR FROM
 THE ROOF WITH OUT A RELIEF VENT ON THE BRANCH AND SHALL
 COMPLY WITH FBC PL. SEC
 918.3.1 HORIZONTAL BRANCHES.
 INDIVIDUAL AND BRANCH-TYPE AIR ADMITTANCE VALVES SHALL
 VENT ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND
 CONNECT TO A HORIZONTAL BRANCH DRAIN. WHERE THE
 HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL CONNECT
 TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE STACK AND
 THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED TO THE
 HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED IN
 ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL BE
 PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. THIS
 IS THE SECOND REQUEST.