| 2016-01-16 08:05:52 | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE A HOT WATER RECIRC SYSTEM TO COMPLY WITH. |
| | FBC PL SEC 607.2 HOT OR TEMPERED WATER SUPPLY TO |
| | FIXTURES. |
| | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| | (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER |
| | 2.WATER HEATER NOTE SHOWS WH BEING SET AT 140 PROVIDE |
| | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| | SET AT 120 TO HAND WASHING SINKS AND 110 FOR PUBLIC |
| | RESTROOMS. PER FBC ENERGY. C404.3 TEMPERATURE CONTROLS. |
| | SERVICE WATER-HEATING EQUIPMENT SHALL BE PROVIDED WITH |
| | CONTROLS TO ALLOW A SETPOINT OF 110F (43C) FOR |
| | EQUIPMENT SERVING DWELLING UNITS AND 90F (32C) FOR |
| | EQUIPMENT SERVING OTHER OCCUPANCIES. THE OUTLET |
| | TEMPERATURE OF LAVATORIES IN PUBLIC FACILITY REST ROOMS |
| | SHALL BE LIMITED TO 110F (43C). |
| | 3. WHAT TEMPERATURE WILL THE WATER BE DRAINING FROM THE |
| | HOT WELL #19 ON KIT SCHEDULE IT SHALL COMPLY WITH FBC |
| | PL. SEC 701.7 WASTE WATER WHERE DISCHARGED INTO THE |
| | BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT |
| | GREATER THAN 140? |
| | 4. SHEET INDEX INDICATES DEMO PLAN BUT IT IS NOT IN |
| | PLAN SET PLEASE PROVIDE. PER WPB AMEND. TO FBC SEC. |
| | 107.2.1 |
| | 5. PROVIDE MANUFACTURE SPECS ON SUB WATER MATER.PER WPB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | 6. LIST MANUFACTURE AND MODEL OF BACKFLOW DEVICES. PER |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 7. ADDRESS ON PLANS IS WRONG PLEASE CORRECT. PER WPB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | 8. AAV ARE NOT ALLOWED ON THE FIRST FLOOR OF THIS |
| | BUILDING. PER FBC PL. SEC |
| | 918.3.1 HORIZONTAL BRANCHES. |
| | INDIVIDUAL AND BRANCH-TYPE AIR ADMITTANCE VALVES SHALL |
| | VENT ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND |
| | CONNECT TO A HORIZONTAL BRANCH DRAIN. WHERE THE |
| | HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL CONNECT |
| | TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE STACK AND |
| | THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED TO THE |
| | HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL BE SIZED |
| | IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED IN |
| | ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL BE |
| | PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. |