2016-01-16 09:06:121ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 APPLIANCES PER THE FBC-2014 FUEL GAS CODE SEC. 304.
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 3. SHOW PIPE SIZING ON EVER Y SECTION OF PIPE ON RISER
 DIAGRAM INCLUDING ALL EXISTING. PER WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
 4. SHOW REGULATORS ON RISER DIAGRAM. PER WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
 5. VENTS AND FRESH AIR INTAKES FOR WATER HEATERS ON SHT
 M-1 DO NOT MATCH SHT P-3 PLEASE CLARIFY. PER WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
  
  