Plan Review Notes
Plan Review Notes For Permit 16010193
Permit Number 16010193
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-14 13:51:231ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 THIS PERMITS APPLICATION FALLS UNDER REPAIRS IN
 EXISTING BUILDING CODE SECTION 607 ELECTRICAL ( THE
 WORK SHALL NOT MAKE THE BUILDING LESS CONFORMING THAN
 IT WAS BEFORE THE REPAIR WAS UNDERTAKEN. )
 FOR FUTURE LOAD CLACS PLEASE INCLUDE MANDATORY LAUNDRY
 CIRCUIT NEC 220.52 (B) LAUNDRY CIRCUIT LOAD. A LOAD OF
 NOT LESS THAN 1500
 VOLT-AMPERES SHALL BE INCLUDED FOR EACH 2-WIRE LAUNDRY
 BRANCH CIRCUIT INSTALLED AS COVERED BY 210.11(C)(2).
 THIS
 LOAD SHALL BE PERMITTED TO BE INCLUDED WITH THE GENERAL
 LIGHTING LOAD AND SUBJECTED TO THE DEMAND FACTORS
 PROVIDED
 IN TABLE 220.42.