| Plan Review Notes For Permit 16010193 |
| Permit Number |
16010193 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-14 13:51:23 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | THIS PERMITS APPLICATION FALLS UNDER REPAIRS IN | | | EXISTING BUILDING CODE SECTION 607 ELECTRICAL ( THE | | | WORK SHALL NOT MAKE THE BUILDING LESS CONFORMING THAN | | | IT WAS BEFORE THE REPAIR WAS UNDERTAKEN. ) | | | FOR FUTURE LOAD CLACS PLEASE INCLUDE MANDATORY LAUNDRY | | | CIRCUIT NEC 220.52 (B) LAUNDRY CIRCUIT LOAD. A LOAD OF | | | NOT LESS THAN 1500 | | | VOLT-AMPERES SHALL BE INCLUDED FOR EACH 2-WIRE LAUNDRY | | | BRANCH CIRCUIT INSTALLED AS COVERED BY 210.11(C)(2). | | | THIS | | | LOAD SHALL BE PERMITTED TO BE INCLUDED WITH THE GENERAL | | | LIGHTING LOAD AND SUBJECTED TO THE DEMAND FACTORS | | | PROVIDED | | | IN TABLE 220.42. |
|