| 2016-02-25 07:18:37 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010176 |
| | ADD: 330 CLEMATIS ST. SUITE # 102 |
| | CONT: C. S. STOPEHENGE CONTRACTOR |
| | TEL: 305-989-1987 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. FEB. 25/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) 3D REQUEST. THE VALUE IS LOW, THE SUB-CONTRACTORS |
| | WORK IS TO BE INCLUDED IN THE VALUE OF THE PROJECT. THE |
| | 1ST PERMIT APPLICATION CAME IN AT A VALUE OF $15,000.00 |
| | THE 2ND APPLICATION AT #2,500.00. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 108.3* BUILDING PERMIT VALUATION. IF, IN |
| | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 3RD REQUEST. 2014 EXISTING BUILDING CODE LEVEL II |
| | 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | SHEET A-2 THE NEW WALL AND DOOR (DOOR # 3) THAT IS |
| | ADDED JUST OUTSIDE OF THE RESTROOM CREATES A CODE |
| | VIOLATION TO THE 2014 FBC-ACCESSIBIITY CODE SECTION |
| | 404.2. MANEUVERING CLEARANCES, FIGURE 404.2.1(A). |
| | PLEASE REVIEW FIGURE 404.2.1(A) THE DOOR SWINGS INTO |
| | THE WORK ROOM, THE 18 INCHES IS TO BE TAKEN ON THE PULL |
| | SIDE OF THE DOOR THE LATCH SIDE. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |