| Plan Review Notes For Permit 16010176 |
| Permit Number |
16010176 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-09 06:07:50 | 1) INDICATE THE EXISTING AND PROPOSED OCCUPANCY TYPE OF | | | THIS SPACE ON THE PLANS PER 2014 FBC SEC.303. | | | 2) PROVIDE FACTORY SIZING CALCULATIONS FROM SCHIER FOR | | | THE SIZE OF THE GREASE INTERCEPTOR. 2014 FPC SEC. | | | 1003.2.CONTACT LEE SCHNEEWEISS AT 561-632-3123.2ND | | | REQUEST. | | | 3) A 4X4X3 TEE IS NOT ACCEPTABLE AS A SAMPLING PORT. | | | EITHER A MANUFACTURED SAMPLING PORT CAN BE INSTALLED OR | | | A 6 INCH TWO WAY CLEANOUT CAN BE INSTALLED PER THE CITY | | | OF WPB ENGINEERING DEPT. STANDARD DWG. GS-7 & GS-7.1. | | | 4) SHOW THE DEVELOPED LENGTH OF THE HOT WATER SYSTEM. A | | | RECIRCULATION LINE MAY BE REQUIRED PER THE 2014 FPC | | | SEC.607.2. | | | 5) SHT. P-2 - FLOOR DRAIN DETAIL - THE MINIMUM REQUIRED | | | AIR GAP SHALL BE NOT LESS THAN TWICE THE EFFECTIVE | | | OPENING OF THE INDIRECT WASTE PIPE PER 2014 FPC SEC. | | | 802.2.1. | | | 6) THE HYDROMECHANICAL GREASE INTERCEPTOR SHALL BE | | | VENTED IN ACCORDANCE WITH 2014 FPC SEC.1003.3.4.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|