Plan Review Notes
Plan Review Notes For Permit 16010176
Permit Number 16010176
Review Stop P
Sequence Number 2
Notes
Date Text
2016-02-09 06:07:501) INDICATE THE EXISTING AND PROPOSED OCCUPANCY TYPE OF
 THIS SPACE ON THE PLANS PER 2014 FBC SEC.303.
 2) PROVIDE FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZE OF THE GREASE INTERCEPTOR. 2014 FPC SEC.
 1003.2.CONTACT LEE SCHNEEWEISS AT 561-632-3123.2ND
 REQUEST.
 3) A 4X4X3 TEE IS NOT ACCEPTABLE AS A SAMPLING PORT.
 EITHER A MANUFACTURED SAMPLING PORT CAN BE INSTALLED OR
 A 6 INCH TWO WAY CLEANOUT CAN BE INSTALLED PER THE CITY
 OF WPB ENGINEERING DEPT. STANDARD DWG. GS-7 & GS-7.1.
 4) SHOW THE DEVELOPED LENGTH OF THE HOT WATER SYSTEM. A
 RECIRCULATION LINE MAY BE REQUIRED PER THE 2014 FPC
 SEC.607.2.
 5) SHT. P-2 - FLOOR DRAIN DETAIL - THE MINIMUM REQUIRED
 AIR GAP SHALL BE NOT LESS THAN TWICE THE EFFECTIVE
 OPENING OF THE INDIRECT WASTE PIPE PER 2014 FPC SEC.
 802.2.1.
 6) THE HYDROMECHANICAL GREASE INTERCEPTOR SHALL BE
 VENTED IN ACCORDANCE WITH 2014 FPC SEC.1003.3.4.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  