| Plan Review Notes For Permit 16010176 |
| Permit Number |
16010176 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-15 13:06:14 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE COST BREAKDOWN TO SHOW COMPLIANCE | | | WITH FBC ACC SEC 202.4.1-202.4.2 | | | 2.PLEASE PROVIDE INSTALLATION GUIDE AND SPEC SHEETS FOR | | | TANKLESS WATER HEATER.PER WPB AMEND TO FBC 107.2.1 | | | 3. BACKFLOW IS REQUIRED FOR COFFE MAKER PER FBC PL SEC | | | 608.16.10 | | | 4 PLEASE PROVIDE SIZING CALCULATIONS FROM SCHIER FOR | | | GREASE INTERCEPTOR YOU CAN CONTACT LEE SCHNEEWEISS PH. | | | 561-632-3123 | | | 5. THE SAMPLING POINTE SHALL BE MIN. OF 6IN WITH NO | | | SUMP ON THE BOTTOM WE RECOMMEND USING A 6IN TWOWAY | | | CLEANOUT WITH 3X6 REDUCING COUPLINGS. | | | 6. THE FLOOR SINK THAT IS SERVING P5+P6 IS NOT VENTED | | | PER FBC PL SEC 901.2.1 YOU CAN USE THE VENT ON P6 AND | | | DRAIN P5 INTO THE FLOOR SINK. |
|