Plan Review Notes
Plan Review Notes For Permit 16010176
Permit Number 16010176
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-15 13:06:141ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC SEC 202.4.1-202.4.2
 2.PLEASE PROVIDE INSTALLATION GUIDE AND SPEC SHEETS FOR
 TANKLESS WATER HEATER.PER WPB AMEND TO FBC 107.2.1
 3. BACKFLOW IS REQUIRED FOR COFFE MAKER PER FBC PL SEC
 608.16.10
 4 PLEASE PROVIDE SIZING CALCULATIONS FROM SCHIER FOR
 GREASE INTERCEPTOR YOU CAN CONTACT LEE SCHNEEWEISS PH.
 561-632-3123
 5. THE SAMPLING POINTE SHALL BE MIN. OF 6IN WITH NO
 SUMP ON THE BOTTOM WE RECOMMEND USING A 6IN TWOWAY
 CLEANOUT WITH 3X6 REDUCING COUPLINGS.
 6. THE FLOOR SINK THAT IS SERVING P5+P6 IS NOT VENTED
 PER FBC PL SEC 901.2.1 YOU CAN USE THE VENT ON P6 AND
 DRAIN P5 INTO THE FLOOR SINK.