| Plan Review Notes For Permit 16010176 |
| Permit Number |
16010176 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-12 08:17:48 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010176 | | | 1/12/16 | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | PROPOSED NEW GELATO SHOP IN ACCORDANCE WITH TABLE 403.3 | | | FBC-14 MECHANICAL. REFER TO SECTION 809.1 RECONFIGURED | | | OR CONVERTED SPACES. | | | ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL | | | SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN | | | ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR | | | MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, MECHANICAL. | | | SHOW ON THE PLAN THE REQUIRED AMOUNT OF OUTDOOR AIR | | | CFM'S PER THE TABLE, AND THE AMOUNT PROVIDED BY THE | | | EXISTING HVAC SYSTEMS. | | | 2) PROVIDE A SCOPE OF WORK AND DETAILS FOR ALL PROPOSED | | | ALTERATIONS TO THE EXISITNG HVAC SYSTEMS (IF APPLICABLE | | | TO THE PROJECT). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|