2016-01-12 08:17:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010176
 1/12/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED NEW GELATO SHOP IN ACCORDANCE WITH TABLE 403.3
 FBC-14 MECHANICAL. REFER TO SECTION 809.1 RECONFIGURED
 OR CONVERTED SPACES.
 ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
 SHOW ON THE PLAN THE REQUIRED AMOUNT OF OUTDOOR AIR
 CFM'S PER THE TABLE, AND THE AMOUNT PROVIDED BY THE
 EXISTING HVAC SYSTEMS.
 2) PROVIDE A SCOPE OF WORK AND DETAILS FOR ALL PROPOSED
 ALTERATIONS TO THE EXISITNG HVAC SYSTEMS (IF APPLICABLE
 TO THE PROJECT).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  