Plan Review Notes
Plan Review Notes For Permit 16010176
Permit Number 16010176
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-21 17:31:411ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 JOB PERMIT NUMBER: 16010176
 JOB ADDRESS: 330 CLEMATIS ST U-102
 WEST PALM BEACH ( GELATO)
 DATE: JAN 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1- PLEASE SITE CURRENT CODE STANDARDS NEC 2011 AND FBC
 2014
 2- PROVIDE PROPER PANEL BOARD MARKINGS IS THIS SINGLE
 OR THREE PHASE SYSTEM? NEC 408.58
 3- THE BRANCH CIRCUIT FEEDING THE EMERGENCY EQUIPMENT
 SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
 LOCAL SWITCHES. NEC 700.12 F (SHOW ON PLANS OR ADD
 NOTE.)
 4- PADDLE FAN INSTALLED OUTSIDE MUST BE PROPERLY
 SUPPORTED IN ACCORDANCE WITH NEC 314.27 C
 5- PROVIDE SHOW WINDOW OUTLET FOR EVERY 12 LINEAR FEET
 OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT ITS
 MAXIMUM WIDTH. NEC 210.62
 6- PROVIDE FIXTURE MEANS OF SUPPORT DETAIL OR NOTE ON
 TO PLANS. NEC 410.36
 7- MANDATORY INTERIOR LIGHTING CONTROLS ARE REQUIRED AS
 PER FBC-E C405 BATHROOMS MUST BE ON OCCUPANCY SENSORS
 8- MANDATORY EXTERIOR LIGHTING CONTROLS FOR SIGNS MUST
 BE ON ASTRONOMICAL TIMER OR COMBINATION OF PHOTOCELL
 AHEAD OF TIMER. FBC-E C405
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
  