Plan Review Notes
Plan Review Notes For Permit 16010174
Permit Number 16010174
Review Stop M
Sequence Number 3
Notes
Date Text
2016-05-31 16:09:193RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010174
 5/31/16
  
 1) THE ARCHITECT'S REVISED AC CALCULATIONS INDICATE A
 6-TON HEAT LOAD, HOWEVER THE PLAN IS SPECIFYING ONLY A
 3-TON SYSTEM AND AN EXISTING THROUGH-THE-WALL UNIT.
 PLEASE INDICATE THE COOLING CAPACITY OF THE EXISTING
 UNIT ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  