| Plan Review Notes For Permit 16010174 |
| Permit Number |
16010174 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-05-31 16:09:19 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010174 | | | 5/31/16 | | | | | | 1) THE ARCHITECT'S REVISED AC CALCULATIONS INDICATE A | | | 6-TON HEAT LOAD, HOWEVER THE PLAN IS SPECIFYING ONLY A | | | 3-TON SYSTEM AND AN EXISTING THROUGH-THE-WALL UNIT. | | | PLEASE INDICATE THE COOLING CAPACITY OF THE EXISTING | | | UNIT ON THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|