2016-04-11 15:50:232ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SCHIER WILL PROVIDE A SITE SPECIFIC CALCULATIONS FOR
 THE INTERCEPTOR YOUR USING, THAT IS WHAT WE ARE LOOKING
 FOR ,ON ANY HYDROMECHANICAL GREASE INTERCEPTOR. YOU CAN
 CONTACT LEE SCHEEWEISS AT 1-800-538-4792 FOR DETAILS
 PER WPB AMEND.TO FBC SEC.107.2.1
  
 2. THE FLOOR SINK SHALL CONNECT TO GREASE INTERCEPTOR.
 PER FBC PL SEC. 1003.1
  
 3. THE HAND SINK IN KITCHEN SHALL CONNECT TO SANITARY
 DOWN STREAM OF BATHROOM GROUP.
 PER FBC PL SEC. 1003.2 + 912.1
  
  
 4. SHOW CLEAN OUTS AND AND SAMPLING PORT ON RISER
 DIAGRAM.
 PER WPB AMEND. TO FBC SEC. 107.2.1