| Plan Review Notes For Permit 16010174 |
| Permit Number |
16010174 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-11 15:50:23 | 2ND REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SCHIER WILL PROVIDE A SITE SPECIFIC CALCULATIONS FOR | | | THE INTERCEPTOR YOUR USING, THAT IS WHAT WE ARE LOOKING | | | FOR ,ON ANY HYDROMECHANICAL GREASE INTERCEPTOR. YOU CAN | | | CONTACT LEE SCHEEWEISS AT 1-800-538-4792 FOR DETAILS | | | PER WPB AMEND.TO FBC SEC.107.2.1 | | | | | | 2. THE FLOOR SINK SHALL CONNECT TO GREASE INTERCEPTOR. | | | PER FBC PL SEC. 1003.1 | | | | | | 3. THE HAND SINK IN KITCHEN SHALL CONNECT TO SANITARY | | | DOWN STREAM OF BATHROOM GROUP. | | | PER FBC PL SEC. 1003.2 + 912.1 | | | | | | | | | 4. SHOW CLEAN OUTS AND AND SAMPLING PORT ON RISER | | | DIAGRAM. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 |
|