| Plan Review Notes For Permit 16010174 |
| Permit Number |
16010174 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-28 14:50:19 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010174 | | | 3/28/16 | | | | | | 1) AC LOAD SUMMARY CALCULATIONS CAN BE SUBMITTED ONLY | | | BY A REGISTERED ENGINEERED WHO MUST PLACE HIS/HER | | | SIGNATURE AND SEAL ON THE DOCUMENT- SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | 2) NO COMPLIANCE DATA WAS LISTED IN THE ENERGY | | | COMPLIANCE FORM FOR THE NEW MINI-SPLIT SYSTEM. | | | 3) 2ND REQUEST FOR VENITLATION AND AIR BALANCE | | | CALCULATIONS TO BE PLACED ON THE PLANS. PROVIDE A | | | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS | | | OF O/A FOR OCCUPANTS AND EXHAUST CFMS FOR THE KITCHEN. | | | 3) INDICATE ON THE PLANS IF THE CONDENSATE DRAINING TO | | | THE EXTERIOR IS TO PERMEABLE GROUND OR TO A DRYWELL. | | | 4) CLARIFY WHERE THE CONDENSER FOR THE MINI-SPLIT | | | SYSTEM IS BEING INSTALLED- ON THE WALL OR ON A SLAB? IF | | | ON THE GROUND PROVIDE A DETAIL FOR INSTALLATION OF A | | | MOUNTING PAD, IF ON THE WALL PROVIDE A DETAIL USING A | | | WALL BRACKET AND SUBMIT AN NOA OR PRODUCT APPROVAL. | | | PLEASE INCLUDE THE WIND LOAD DESIGN CRITERIA AS | | | OUTLINED IN SECTION 1609 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|