2016-03-28 14:50:192ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010174
 3/28/16
  
 1) AC LOAD SUMMARY CALCULATIONS CAN BE SUBMITTED ONLY
 BY A REGISTERED ENGINEERED WHO MUST PLACE HIS/HER
 SIGNATURE AND SEAL ON THE DOCUMENT- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) NO COMPLIANCE DATA WAS LISTED IN THE ENERGY
 COMPLIANCE FORM FOR THE NEW MINI-SPLIT SYSTEM.
 3) 2ND REQUEST FOR VENITLATION AND AIR BALANCE
 CALCULATIONS TO BE PLACED ON THE PLANS. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF O/A FOR OCCUPANTS AND EXHAUST CFMS FOR THE KITCHEN.
 3) INDICATE ON THE PLANS IF THE CONDENSATE DRAINING TO
 THE EXTERIOR IS TO PERMEABLE GROUND OR TO A DRYWELL.
 4) CLARIFY WHERE THE CONDENSER FOR THE MINI-SPLIT
 SYSTEM IS BEING INSTALLED- ON THE WALL OR ON A SLAB? IF
 ON THE GROUND PROVIDE A DETAIL FOR INSTALLATION OF A
 MOUNTING PAD, IF ON THE WALL PROVIDE A DETAIL USING A
 WALL BRACKET AND SUBMIT AN NOA OR PRODUCT APPROVAL.
 PLEASE INCLUDE THE WIND LOAD DESIGN CRITERIA AS
 OUTLINED IN SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER