Plan Review Notes
Plan Review Notes For Permit 16010174
Permit Number 16010174
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-22 13:42:401) SINCE THE OCCCUPANT LOAD IS UNDER 50 PERSONS, THIS
 IS CONSIDERED A "B" OCCUPANCY, NOT AN A-2. 2014 FBC
 SEC.303.1.1.
 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZE OF THE GREASE TRAP.2014 FPC 1003.2.CONTACT LEE
 SCHNEEWEISS AT 1-800-538-4792.
 3) THE PLAN NOTES THAT THE GAS IS LP BUT THERE IS ALSO
 AN EXISTING GAS METER. CLARIFY.
 4) THE PLANS CALL OUT AN11" WATER COLUMN WITH 0.5 INCH
 PRESSURE DROP BUT THE GAS TABLE THAT IS REFERENCED IS
 FOR A 10 PSI SYSTEM WITH A PRESSURE DROP OF 3 PSI.
 CLARIFY.
 5) THE PLANS NOTE A DEVELOPED LENGTH OF 80 FT. BUT THE
 RISER SHOWS 100 FT. CLARIFY.
 6) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE LINE OF
 THE GREASE INTERCEPTOR AND MUST BE ACCESSIBLE FROM THE
 EXTERIOR OF THE BUILDING.A DETAIL FROM THE CITY'S
 ENGINEERING DEPT. HAS BEEN INCLUDED IN THE PLAN PACKAGE
 FOR YOUR REVIEW.
 7) THE SANITARY RISER SHOWS THE FLOOR SINK ON A WET
 VENT. THIS VIOLATES 2014 FPC SEC.912.1.
 8) THE CAN WASH IS NOT VENTED.
 9) SIZE ALL THE VENTS ON THE SANITARY RISER.
 10) SUBMIT MANUF. SPECIFICATIONS FOR THE GAS
 APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED. 2014
 FGC SEC.301.3.
  