| Plan Review Notes For Permit 16010174 |
| Permit Number |
16010174 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-22 13:42:40 | 1) SINCE THE OCCCUPANT LOAD IS UNDER 50 PERSONS, THIS | | | IS CONSIDERED A "B" OCCUPANCY, NOT AN A-2. 2014 FBC | | | SEC.303.1.1. | | | 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR | | | THE SIZE OF THE GREASE TRAP.2014 FPC 1003.2.CONTACT LEE | | | SCHNEEWEISS AT 1-800-538-4792. | | | 3) THE PLAN NOTES THAT THE GAS IS LP BUT THERE IS ALSO | | | AN EXISTING GAS METER. CLARIFY. | | | 4) THE PLANS CALL OUT AN11" WATER COLUMN WITH 0.5 INCH | | | PRESSURE DROP BUT THE GAS TABLE THAT IS REFERENCED IS | | | FOR A 10 PSI SYSTEM WITH A PRESSURE DROP OF 3 PSI. | | | CLARIFY. | | | 5) THE PLANS NOTE A DEVELOPED LENGTH OF 80 FT. BUT THE | | | RISER SHOWS 100 FT. CLARIFY. | | | 6) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE LINE OF | | | THE GREASE INTERCEPTOR AND MUST BE ACCESSIBLE FROM THE | | | EXTERIOR OF THE BUILDING.A DETAIL FROM THE CITY'S | | | ENGINEERING DEPT. HAS BEEN INCLUDED IN THE PLAN PACKAGE | | | FOR YOUR REVIEW. | | | 7) THE SANITARY RISER SHOWS THE FLOOR SINK ON A WET | | | VENT. THIS VIOLATES 2014 FPC SEC.912.1. | | | 8) THE CAN WASH IS NOT VENTED. | | | 9) SIZE ALL THE VENTS ON THE SANITARY RISER. | | | 10) SUBMIT MANUF. SPECIFICATIONS FOR THE GAS | | | APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED. 2014 | | | FGC SEC.301.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|