2016-01-12 12:24:521ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010174
 01/12/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 MINI-SPLIT SYSTEM IN COMPLIANCE WITH SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING AND
 PROVIDE VENTILATION AND AIR BALANCE CALCULATIONS ON THE
 PLAN IN ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 PLEASE NOTE THE EXHAUST SYSTEM FOR THE KITCHEN HOOD
 MUST BE INCLUDED IN THE CALCULATIONS.
 3) PLACE A NOTE ON THE PLAN INDICATING THE KITCHEN HOOD
 AND FIRE SUPPRESSION WILL BE DONE UNDER SEPARATE
 PERMIT.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 MINI-SPLIT AIR HANDLER IN THE DINING ROOM- SHOW THE
 PIPING RUN AND DISCHARGE LOCATION.
 5) PROVIDE WIND LOAD TIE-DOWN ENGINEERING FPOR THE MINI
 SPLIT CONDENSER PER SECTION 301.15 FBC-14 MECHANICAL.
 6) PROVIDE AN EXHAUST VENTILATION SYTEM FOR THE NEW
 TOILET ROOM PER TABLE 403.3.
 7) IN ACCORDANCE WITH SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION, PROVIDE ENERGY CALCULATIONS USING EITHER
 THE PERFORMANCE OR PRESCRIPTIVE COMPLIANCE PATHS- SEE
 SECTION C101.5.1
  