| Plan Review Notes For Permit 16010174 |
| Permit Number |
16010174 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-11 16:13:26 | REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. THE FLOOR PLAN SHOWS THE TANKLESS HEATER BEFORE | | | ANSUL VALVE ON THE EXTERIOR OF THE BUILDING. THE RISER | | | SHOWS TANKLESS HEATER AFTER THE ANSUL VALVE PLEASE | | | CLARIFY. | | | PER WPB AMEND. TO FBC SEC 107.2.1 | | | | | | 2. NOTE ON GAS PLAN STILL IS REFERENCING A TABLE FOR 10 | | | PSI PROPANE GAS PLEASE CORRECT. | | | PER WPB AMEND. TO FBC SEC 107.2.1 | | | | | | 3.SYSTEM IS UNDERSIZED PER FBC FUEL GAS TABLE 402.4(2) | | | | | | 4. 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. |
|