2016-04-11 16:13:26REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. THE FLOOR PLAN SHOWS THE TANKLESS HEATER BEFORE
 ANSUL VALVE ON THE EXTERIOR OF THE BUILDING. THE RISER
 SHOWS TANKLESS HEATER AFTER THE ANSUL VALVE PLEASE
 CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
  
 2. NOTE ON GAS PLAN STILL IS REFERENCING A TABLE FOR 10
 PSI PROPANE GAS PLEASE CORRECT.
 PER WPB AMEND. TO FBC SEC 107.2.1
  
 3.SYSTEM IS UNDERSIZED PER FBC FUEL GAS TABLE 402.4(2)
  
 4. 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.