| Date |
Text |
| 2016-02-10 14:27:33 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. UPDATE ALL APPLICABLE CODES TO REFLECT NEW FBC 2014 | | | 5TH EDITION SET AND NFPA 70 NEC 2011 | | | 2. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE. | | | 3. SHOW WINDOW RECEPTACLES REQUIRED PER NEC 220.14G AND | | | 210.62 | | | 4. HOOD SUPPRESSION TO BE UNDER SEPARATE PERMIT. A NOTE | | | WILL SUFFICE | | | 5. PER FBC 107 MINIMUM PLAN REVIEW CRITERIA, SHOW ALL | | | EXISTING AND NEW OUTLETS WITH CIRCUIT DESIGNATIONS. | | | 6. LABEL PANEL SCHEDULE PER SPECIFIC PURPOSE OR USE. | | | GENERAL LIGHTING AND RECEPTACLE ID DOES NOT MEET THE | | | INTENT. NEC 408.4A | | | 7. LABEL ALL KITCHEN OUTLETS TO BE GFCI PROTECTED ON | | | FLOOR PLAN. FBC 107 NEC 210.8B | | | 8. PLEASE SHOW THE GEC SIZE AT THE NEW SERVICE AND | | | PROVIDE AN INTERSYSTEM BONDING TERMINATION. NEC 250.94 | | | AND NEC 250.66 | | | 9. PLEASE CLARIFY IF THIS BUILDING IS BEING SERVED BY | | | MULTIPLE ELECTRICAL SERVICES, AS A NEW ONE IS SHOWN. | | | NEC 230.2 | | | 10. SHOW AIC AND VOLTAGE DROP CALCULATIONS FOR THE NEW | | | SERVICE PER FBC EC 405.7 | | | 11. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|