Plan Review Notes
Plan Review Notes For Permit 16010174
Permit Number 16010174
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-10 14:27:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL APPLICABLE CODES TO REFLECT NEW FBC 2014
 5TH EDITION SET AND NFPA 70 NEC 2011
 2. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE.
 3. SHOW WINDOW RECEPTACLES REQUIRED PER NEC 220.14G AND
 210.62
 4. HOOD SUPPRESSION TO BE UNDER SEPARATE PERMIT. A NOTE
 WILL SUFFICE
 5. PER FBC 107 MINIMUM PLAN REVIEW CRITERIA, SHOW ALL
 EXISTING AND NEW OUTLETS WITH CIRCUIT DESIGNATIONS.
 6. LABEL PANEL SCHEDULE PER SPECIFIC PURPOSE OR USE.
 GENERAL LIGHTING AND RECEPTACLE ID DOES NOT MEET THE
 INTENT. NEC 408.4A
 7. LABEL ALL KITCHEN OUTLETS TO BE GFCI PROTECTED ON
 FLOOR PLAN. FBC 107 NEC 210.8B
 8. PLEASE SHOW THE GEC SIZE AT THE NEW SERVICE AND
 PROVIDE AN INTERSYSTEM BONDING TERMINATION. NEC 250.94
 AND NEC 250.66
 9. PLEASE CLARIFY IF THIS BUILDING IS BEING SERVED BY
 MULTIPLE ELECTRICAL SERVICES, AS A NEW ONE IS SHOWN.
 NEC 230.2
 10. SHOW AIC AND VOLTAGE DROP CALCULATIONS FOR THE NEW
 SERVICE PER FBC EC 405.7
 11. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  