Plan Review Notes
Plan Review Notes For Permit 16010142
Permit Number 16010142
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-13 09:51:59THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. CITY OF WPB AMENDMENTS TO THE FBC SECTION 107.2.1
 REQUIRED THAT DOCUMENTS BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DRAWINGS.
 2. CITY OF WPB AMENDMENTS TO THE FBC SECTION 107.2.1.4
 REQUIRE THAT SUBMITTAL BE CLEAR AND LEGIBLE AND BEAR A
 FONT CAPABLE OF BEING READ AFTER BEING SCANNED FOR
 RECORDS RETENTION. THE SUBMITTED DRAWINGS HAVE A VERY
 SMALL FONT.
 3. I CAN ACCEPT THE ONE LINE DRAWINGS AS IS BUT IT MUST
 BE ACCOMPANIED BY A SITE SPECIFIC DRAWING INDICATING
 THE LOCATION OF EVERY COMPONENT OF THIS INSTALLATION.
 4. YOU SHALL INDICATE ON THE DRAWINGS HOW YOU PROPOSE
 TO RUN THE PV SOURCE CONDUCTORS TO THE INVERTERS. WILL
 THEY BE INSIDE THE ROOF (SHOW PENETRATIONS AND
 SEALING). IF ON THE ROOF INDICATE CONDUCTOR INSULATIONS
 ETC.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  