2016-01-09 05:21:291) THE PLANS DO NOT SHOW ANY PROVISIONS FOR IRRIGATION.
 WILL A CONNECTION BE MADE TO THE EXISITING IRRIGATION
 SYSTEM TO SERVE THE NEW LANDSCAPING? IF CONNECTING TO
 AN EXISTING SYSTEM, SHOW THE LOCATION, SIZE AND TYPE OF
 THE EXISTING BFP DEVICE AND CONTROLLER AND SHOW THE
 LOCATION OF THE REQUIRED RAIN SENSOR. IF THE IRRIGATION
 SYSTEM WILL HAVE IT'S OWN SEPARATE CONNECTION TO THE
 POTABLE WATER SYSTEM, THEN A BACKFLOW PREVENTION DEVICE
 AND RAIN SENSOR & CONTROLLER SHALL SHALL BE INSTALLED.
 THE BFP DEVICE SHALL COMPLY WITH THE CWPB CROSS
 CONNECTION MANUAL.SHOW THE LOCATION OF THE NEW
 CONTROLLER, BFP DEVICE AND THE RAIN SENSOR IF
 APPLICABLE.
 2) SUBMIT AN IRRIGATION PLAN FOR REVIEW. WPB AMEND. TO
 FBC SEC. 107.2.1.
  