| Plan Review Notes For Permit 16010128 |
| Permit Number |
16010128 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-07 16:57:52 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 1- FLAT ROOF NOA 14-0224.03 SUBMITTED: | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION | | | (2014). | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 14-0224.03 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO | | | MEET THE DESIGN PRESSURES OF SEC.R301 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | NOTE: NOTICE OF COMMENCEMENT WILL BE REQUIRED FOR THE | | | ROOFING WORK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|