2016-01-25 14:15:371ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010118
 01/25/16
  
 1) PROVIDE REFRIGERATION EQUIPMENT SCHEDULES THAT
 INCLUDE THE MAKES AND MODELS OF THE EVAPORATOR AND
 CONDENSER, AND THE TYPE AND QUANITY OF REFRIGERANT IN
 THE SYSTEM.
 2) SHOW THE LOCATION OF THE CONDENSER ON THE PLAN, AND
 PROVIDE SITE-SPECIFIC ENGINEERING FOR THE BRACKET
 ATTACHMENT, AND TIE-DOWN OF THE CONDENSER TO THE
 BRACKET. PLEASE NOTE THE SUBMITTAL FOR THE MIAMI-TECH
 CU BRACKET HAS A COPIED ENGINEER'S SEAL- AN ORIGINAL
 SEAL AND SIGNATUTRE IS REQUIRED PER FAC SECTION
 61G15-23.002.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  