Plan Review Notes
Plan Review Notes For Permit 16010118
Permit Number 16010118
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-02 07:45:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010118
 ADD: 330 SOUTHERN BLVD.
 CONT: PRIME MECHANICAL SERVICES
 TEL: 954-448-8870
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 02/ 2016
 ACTION: DENIED
  
 1) TARNOWSKI ENGINEERING SHEET 1 OF 2 SHOWS THE SIZE OF
 THE SLAB BUT THERE IS NO CROSS SECTION OF THE SLAB
 SHOWING THE DEPTH SLAB REINFORCING NOR THE THICKENED
 MONOLITHIC FOUNDATION. 2014 FBC-B 1809.4 DEPTH AND
 WIDTH OF FOOTINGS. THE MINIMUM DEPTH OF FOOTINGS BELOW
 THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES (305
 MM). WHERE APPLICABLE, THE REQUIREMENTS OF SECTION
 1809.5 SHALL ALSO BE SATISFIED. THE MINIMUM WIDTH OF
 FOOTINGS SHALL BE 12 INCHES.
  
 2) 2014 FBC-B 1810.3.9.2 REQUIRED REINFORCEMENT. WHERE
 SUBJECT TO UPLIFT OR WHERE THE REQUIRED MOMENT STRENGTH
 DETERMINED USING THE LOAD COMBINATIONS OF SECTION
 1605.2
  
 3) 2014 FBC-B 1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION.
  
 4) MIAMI TECH SHEET FOR A CONDENSOR BRACKET IS A
 PHOTO-COPIED SEAL NOT ORIGINAL, SEAL STATES THAT IT IS
 NOT VALID UNLESS IT IS A RAISED SEAL. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS/ EFFECTIVE DATE
 05/06/2009
  
 5) PLEASE SHOW ON THE FLOOR SLAB PLANS WHERE THE
 CONDENSOR AND CONDENSOR BRACKET ARE TO BE INSTALLED,
 LOCATED IN A WALL ZONE 4 OR WALL ZONE 5?
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 6) TARNOWSKI ENGINEERING SHEET 1 OF 2 SHOWS A NEW
 PROPOSED RAMP OF 11 FEET LONG. PLEASE PROVIDE
 COMPLIANCE WITH 2014 FBC-B :
 1010.1 SCOPE.
 THE PROVISIONS OF THIS SECTION SHALL APPLY TO RAMPS
 USED AS A COMPONENT OF A MEANS OF EGRESS.
  
 EXCEPTIONS:
  
 1. OTHER THAN RAMPS THAT ARE PARTS OF ACCESSIBLE ROUTES
 PROVIDING ACCESS IN ACCORDANCE WITH THE PROVISIONS OF
 THE FLORIDA BUILDING CODE, ACCESSIBILITY, RAMPED AISLES
 WITHIN ASSEMBLY ROOMS OR SPACES SHALL CONFORM TO THE
 PROVISIONS IN 1028.11.
  
 2. CURB RAMPS NOT SUBJECT TO FLORIDA BUILDING CODE,
 ACCESSIBILITY, SHALL COMPLY WITH ICC ANSI A117.1.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  