| Plan Review Notes For Permit 16010117 |
| Permit Number |
16010117 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-03-14 10:48:32 | APPROVED WITH EXCEPTIONS, WHICH ARE NOTED ON PLAN: | | | | | | 1) PROVIDE ACCURATE LOAD CALCULATION FOR PANEL AND | | | SERVICE TO SHOW CAPACITY IS ADEQUATE. NEC 220 | | | 2) EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) | | | 3) CIRCUIT NUMBER B-11 IS SHOWN FOR RECEPTACLE OUTLETS | | | AND FOR AHU-3. CLARIFY AND/OR CORRECT. FBC 107.2.1 |
|