| 2017-04-14 16:19:50 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010117 |
| | ADD: 431 BUNKER RD. |
| | CONT: TBD |
| | TEL: 561-603-0434 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. APRIL 14/ 2017 |
| | ACTION: DENIED |
| | |
| | 1A) 3ND REQUEST. THE SUBMITTED PAPERWORK IS FOR TAX |
| | PURPOSES ONLY, IT IS NOT A UNITY OF TITLE, IT HAS BEEN |
| | REVIEWED BY BOTH MANUEL GONZALEZ AND VINCENT J NOEL. |
| | 1B) COMPLIED. THE PERMIT APPLICATION INDICATES WORK |
| | UNDER THIS PERMIT WILL BE LOCATED AT 431 BUNKER BY THE |
| | PCN 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARS |
| | THIS INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE |
| | LOT JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT |
| | 417 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCREPANCY |
| | IN INFORMATION. ADDITIONAL INFORMATION |
| | REQUIRED.107.2.1.3. |
| | |
| | 2) COMPLIED. THE COVERSHEET, A-000 INDICATES THE PLANS |
| | UNDER THE HEADING APPLICABLE CODES IS DESIGNED TO THE |
| | 2014 FBC-B BUT UNDER THE GENERAL NOTES THE PLANS |
| | INDICATE THE DESIGN IS UNDER THE 2007 FBC EDITION. |
| | PLEASE UPDATE ALL REFERENCES TO THE 2007 FBC. THE 2014 |
| | FBC OR THE 5TH EDITION OF THE FLORIDA BUILDING CODE WAS |
| | ADOPTED STATEWIDE ON JUNE 30/2015. |
| | |
| | 3A) 3RD REQUEST.431 BUNKER RD. THE COVERSHEET, A-000 |
| | INDICATES WITH THE PROPOSED 1,680 SQ. FT. ADDITION TO |
| | AN EXISTING 7909 SQ. FOOTAGE EXISTING BUILDING TOTALING |
| | 9,589 SQ. FT. W/ MEZZANINE INCLUDED. THE ADDITION |
| | TRANSGRESSES THE PROPERTY LINE AND THAT WILL REQUIRE |
| | THE UNITY OF TITLE. THE OTHER BUILDING LOCATED AT 417 |
| | BUNKER WILL BECOME A SEPARATE BUILDING WITH A 3 HOUR |
| | FIRE WALL THAT WILL MEET ALL OF THE FIRE WALL |
| | REQUIREMENTS. TO BE DISCUSSED LATER ON IN THIS REVIEW. |
| | |
| | UNITY OF TITLE. |
| | THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| | BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'. A 'UNITY OF TITLE' SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT |
| | APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 3B) THE SECOND ISSUE THAT WILL NEED TO BE ADDRESSED IS |
| | THE 431 BUNKER RD. BUILDING BEING DECLARED BUILDING |
| | TYPE VB AND A S1 STORAGE OCCUPANCY OF 9,589 SQ. FT. |
| | NON-SPRINKLERED BUILDING(BUILDING # 1). IN THE 2014 |
| | FBC-B TABLE 503 ALLOWS FOR THIS OCCUPANCY AND BUILDING |
| | TYPE AN ALLOWABLE 9,000 SQ. FT. PLEASE PROVIDE HOW |
| | COMPLIANCE WITH TABLE FBC-B 503 AND BUILDING AREA |
| | MODIFICATIONS FOR THIS BUILDING AS WELL THE BUILDING AT |
| | 417 BUNKER RD. WITH AN AREA OF 9805 SQ. FT. (BUILDING # |
| | 2). |
| | |
| | 4) NEW COMMENT. SHEET A-201 THERE IS A DISCREPANCY IN |
| | THE PLANS. THE BUILDING AT 431 BUNKER RD. ON THE |
| | EXISTING BUILDING SHOW A DOOR THROUGH INTO THE NEW |
| | ADDITION (PROPOSED PLAN) EAST SIDE OF THE EXISTING |
| | BUILDING. UNDER THE ISSUED PERMIT 14090842 ON THE EAST |
| | WALL THERE WAS NO DOOR. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION ABOUT THIS OPENING. 107.2.1.3. |
| | |
| | 5) 2ND REQUEST. THE SUBMITTED ROOFING PRODUCT APPROVAL |
| | REPORT FL 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION |
| | EVERGUARD PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF |
| | 34 HAS CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF |
| | THE SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE |
| | APPENDIX AS TO WHICH WILL BE USED IN THE ROOF |
| | APPLICATION. NOTE IDENTIFY THE SUB-SYSTEM AND NOT THE |
| | POUNDS PER SQUARE FOOT AND IF THERE IS A ASTERISK OR |
| | NOT. PAGE 4 OF 5 LIMITATION 5.8 SYSTEMS MARKED WITH A |
| | ASTERISK ENHANCED FASTENING IS NOT ALLOWED. |
| | SHEET A-401 INDICATES THE USE OF ROOF TOP INSULATION OF |
| | R-30/ METAL B DECK. |
| | |
| | 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |