| Plan Review Notes For Permit 16010117 |
| Permit Number |
16010117 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-22 12:07:38 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010117 | | | 3/22/16 | | | | | | 1) PLEASE CLARIFY WHY THE PROPOSED ADDITION PROJECT HAS | | | BEEN CLASSIFIED AS A "RENOVATION TO EXISTING BUILDING" | | | IN THE PROJECT SUMMARY DATA SHOWN ON PAGE 2 OF THE | | | ENERGYGAUGE SUBMITTAL. | | | 2) PROVIDE ENGINEERED DETAILS FOR INSTALLATION OF THE | | | NEW CONDENSER PAD AND TIE DOWN OF THE NEW CU TO THE | | | PAD- SECTION 301.15. | | | 3) THERE IS A DETAIL ON SHEET A-202 SHOWING AN OPENING | | | INTO THE MAIN BUILDING FROM THE PROPOSED ADDITION: | | | PLEASE NOTE A FIRE SPRINKLER MAY BE REQUIRED FOR THE | | | BUILDING PER SECTION 903.2.9 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|