| 2016-01-15 14:47:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET - 201 - ON THE DOOR SCHEDULE UNDER HARDWARE |
| | SET THE NUMBER 1 IS PROVIDED. THERE IS NO INDICATION OF |
| | WHAT THAT # 1 REPRESENTS. PLEASE PROVIDE THE HARDWARE |
| | SET TYPE AND LOCKING MECHANISM THAT COMPLIES WITH NFPA |
| | 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | 2. SHEET - 201 - THERE IS NOT INDICATION OF AN EXIT |
| | SIGN AT THE NEW INSTALLED DOOR COMPLYING WITH NFPA 101, |
| | CHAPTER 7, MEANS OF EGRESS. |
| | |
| | 3. SHEET - 201 - THERE IS NO INDICATION OF EMERGENCY |
| | LIGHTING ALONG THE PATH OF EGRESS COMPLYIING WITH NFPA |
| | 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | 4. SHEET 202 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE |
| | IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |