| Date |
Text |
| 2016-02-02 13:59:53 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | PROVIDE AN ELECTRICAL PLAN WITH THE FOLLOWING: |
| | ELECTRICAL RISER PLAN SHOWING ALL FEEDERS, DISCONNECTS |
| | AND PANEL BOARDS |
| | LOCATION OF THE ELECTRICAL SERVICE AND MAIN |
| | DISCONNECTS |
| | LOCATION OF ALL ELECTRICAL PANELBOARDS |
| | SAFE WORKING SPACE AT ELECTRICAL DISCONNECTS AND |
| | PANELBOARDS |
| | EXIT AND EMERGENCY ILLUMINATION |
| | |
| | PROVIDE ELECTRIC NOTES ON THE PLAN INDICATING THE |
| | FOLLOWING: |
| | GENERAL PURPOSE RECEPTACLES INSTALLED IN THE |
| | BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS, WITHIN SIX |
| | FEET OF SINKS,AT ELECTRIC DRINKING FOUNTAINS, AND |
| | VENDING MACHINES ARE GFCI PROTECTED. |
| | ALL DISCONNECTS SHALL BE LEGIBLY MARKED TO INDICATE |
| | THEIR PURPOSE. |
| | |
| | PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO |
| | THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS |
| | PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY |
| | CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| | |
| | VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY |
| | BACKUP. FBC ENERGY CONSERVATION 505.2 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | CODE REFERENCES: |
| | FBC EXISTING BUILDING 908.2, 908.3, 908.4 |
| | NEC 110.22, 110.26, 210. 8, 215.5, 422.51, 422.52 |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | |
| | |
| | |
| | |