| 2016-01-22 15:46:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010117 |
| | ADD: 431 BUNKER RD. |
| | CONT: TBD |
| | TEL: 561-603-0434 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 22/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES WORK UNDER THIS |
| | PERMIT WILL BE LOCATED AT 431 BUNKER BY THE PCN |
| | 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARSTHIS |
| | INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE LOT |
| | JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT 417 |
| | BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCRPANCY IN |
| | INFORMATION. ADDITIONAL INFORMATION REQUIRED.107.2.1.3. |
| | |
| | 2) THE COVERSHEET, A-000 INDICATES THE PLANS UNDER THE |
| | HEADING APPLICABLE CODES IS DESIGNED TO THE 2014 FBC-B |
| | BUT UNDER THE GENERAL NOTES THE PLANS INDICATE THE |
| | DESIGN IS UNDER THE 2007 FBC EDITION. PLEASE UPDATE ALL |
| | REFERENCES TO THE 2007 FBC. THE 2014 FBC OR THE 5TH |
| | EDITION OF THE FLORIDA BUILDING CODE WAS ADOPTED |
| | STATEWIDE ON JUNE 30/2015. |
| | |
| | 3) THE COVERSHEET, A-000 INDICATES WITH THE PROPOSED |
| | 1,6778 SQ. FT. ADDITION THE TOTAL SQ. FOOTAGE OF THE |
| | BUILDING IS 19,389 SQ. FT. THE 431 BUNKER RD. BUILDING |
| | WITH MEZZANINE SQ. FOOTAGE IS 7912 SQ, FT. THE 417 |
| | BUNKER RD. BUILDING FROM THE PROPERTY APPRAISERS SITE |
| | IS 9780 SQ. FT. PLUS THE NEW PROPOSED ADDTION OF 1,680 |
| | SQ. FT. IS 19,372 SQ. FT. THIS MEANS THE BUILDINGS ARE |
| | CROSSING OVER PROPERTY LINES AND WILL REQUIRE A UNITITY |
| | OF TITLE. THE OTHER ISSUE SHEET A-202 SHOWS NEW |
| | OPENJNGS IN THE PROPERTY LINE WALL. |
| | |
| | UNITY OF TITLE. |
| | THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| | BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'. A 'UNITY OF TITLE' SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT |
| | APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 4) THE COVERSHEET, A-000 INDICATES THE TOTAL SQUARE |
| | FOOT AREA OF THE COMBINED BUILDINGS TO ENCOMPASS 19,389 |
| | SQUARE FEET. PLEASE SEE THE 2014 FBC-EXISITNG BUILDING |
| | SECTION 1101.2 CREATION OR EXTENSION OF NONCONFORMITY. |
| | AN ADDITION SHALL NOT CREATE OR EXTEND ANY |
| | NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE |
| | ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY, |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR |
| | THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL |
| | SYSTEMS. |
| | |
| | 4A) PLEASE PROVIDE WITH THE TOTAL COMBINED AREA OF THE |
| | 2 BUILDINGS (417 & 431 BUNKER) OF 19,389 SQ. FT. THE |
| | MINIMUM BUILDING TYPE SEE 2014 FBC-B 503. |
| | 1102.2 AREA LIMITATIONS. NO ADDITION SHALL INCREASE THE |
| | AREA OF AN EXISTING BUILDING BEYOND THAT PERMITTED |
| | UNDER THE APPLICABLE PROVISIONS OF CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE, BUILDING FOR NEW BUILDINGS |
| | UNLESS FIRE SEPARATION AS REQUIRED BY THE FLORIDA |
| | BUILDING CODE, BUILDING IS PROVIDED. |
| | |
| | 4B) UNKNOWN IF BUILDING ADDRESSED 417 BUNKER IS FIRE |
| | SPRINKLERED? THE BUILDING AT 431 BUNKER IS |
| | NON-SPRINKLERED CURRENTLY. PLEASE SEE THE 2014 EXISITNG |
| | BUILDING CODE SECTION 1102.3 FIRE PROTECTION SYSTEMS. |
| | EXISTING FIRE AREAS INCREASED BY THE ADDITION SHALL |
| | COMPLY WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, |
| | BUILDING. NOT ONLY IS THERE AN ADDITION BUT A UNITITY |
| | OF TITLE INCREASING THE SIZE OF THE BUILDING TO OVER |
| | 19,000 SQUARE FEET. |
| | |
| | 2014 FBC-B [F] 903.2.9 GROUP S-1. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL |
| | BUILDINGS CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF |
| | THE FOLLOWING CONDITIONS EXISTS: |
| | 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEE. |
| | 5. A GROUP S-1 OCCUPANCY USED FOR THE STORAGE OF |
| | UPHOLSTERED FURNITURE OR MATTRESSES EXCEEDS 2,500 |
| | SQUARE FEET. |
| | |
| | 5) THE SUBMITTED ROOFING PRODUCT APPROVAL REPORT FL |
| | 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION EVERGUARD |
| | PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF 34 HAS |
| | CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF THE |
| | SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE APPENDIX |
| | AS TO WHICH WILL BE USED IN THE ROOF APPLICATION. NOTE |
| | IDENTIFY THE SUB-SYSTEM AND NOT THE POUNDS PER SQUARE |
| | FOOT AND IF THERE IS A ASTERISK OR NOT. PAGE 4 OF 5 |
| | LIMITATION 5.8 SYSTEMS MARKED WITH A ASTERISK ENHANCED |
| | FASTENING IS NOT ALLOWED. |
| | |
| | 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |